Transformer components impact on compatibility of measured PDs: comparison of IEC60270 and RF methods. Issue 1 (4th February 2019)
- Record Type:
- Journal Article
- Title:
- Transformer components impact on compatibility of measured PDs: comparison of IEC60270 and RF methods. Issue 1 (4th February 2019)
- Main Title:
- Transformer components impact on compatibility of measured PDs: comparison of IEC60270 and RF methods
- Authors:
- Firuzi, Keyvan
Vakilian, Mehdi
Phung, B. Toan
Blackburn, Trevor - Abstract:
- Abstract : Power transformer partial discharge signal measurement using Radio Frequency method has advantages over IEC 60270 'apparent charge' measurement method for online monitoring due to greater immunity against external interference. However, the lack of a well‐defined calibration relationship between the two methods is main disadvantage of RF method. Simultaneous measurements, using these two methods, carried out on various transformer PD source models, in laboratory, to investigate main parameters that affect the relationship of results of these two methods. In this paper, factors that influence this relationship are classified into three groups: (i) type of PD sources, (ii) transformer windings as PD signal transmitter, and (iii) the inner structure of the transformer. Firstly, the relationship between these two methods has been investigated for some simple types of PD sources. Subsequently, by adding the winding structure model to the void, which is the PD source, its impact on each measurement method and the relationship between them have been studied. The impact of inner structure on the relation between the two methods is compensated through a formula which is proposed as a means for calibration of the RF partial discharge measurement setup. However to compensate for internal insulating system effects more research is required.
- Is Part Of:
- High voltage. Volume 4:Issue 1(2019)
- Journal:
- High voltage
- Issue:
- Volume 4:Issue 1(2019)
- Issue Display:
- Volume 4, Issue 1 (2019)
- Year:
- 2019
- Volume:
- 4
- Issue:
- 1
- Issue Sort Value:
- 2019-0004-0001-0000
- Page Start:
- 33
- Page End:
- 40
- Publication Date:
- 2019-02-04
- Subjects:
- transformer windings -- power transformers -- partial discharge measurement -- radiofrequency interference
RF probe -- detection methods -- RF PD measurement setup -- calibration method -- transformer components impact -- RF method -- power transformer partial discharge signal measurement -- radio‐frequency method -- IEC60270 apparent charge measurement method -- transformer PD source models -- transformer windings -- PD signal transmitter -- winding structure model -- transformer tank -- transformer inner structure -- internal insulating system
High voltages -- Periodicals
621.3191 - Journal URLs:
- http://ieeexplore.ieee.org/Xplore/home.jsp ↗
https://ietresearch.onlinelibrary.wiley.com/journal/23977264 ↗
http://digital-library.theiet.org/content/journals/hve ↗ - DOI:
- 10.1049/hve.2018.5067 ↗
- Languages:
- English
- ISSNs:
- 2397-7264
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4307.369710
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 23472.xml