Affordable measures to monitor and alarm nosocomial SARS‐CoV‐2 infection due to poor ventilation. (28th June 2021)
- Record Type:
- Journal Article
- Title:
- Affordable measures to monitor and alarm nosocomial SARS‐CoV‐2 infection due to poor ventilation. (28th June 2021)
- Main Title:
- Affordable measures to monitor and alarm nosocomial SARS‐CoV‐2 infection due to poor ventilation
- Authors:
- Lu, Yiran
Li, Yifan
Zhou, Hao
Lin, Jinlan
Zheng, Zhuozhao
Xu, Huji
Lin, Borong
Lin, Minggui
Liu, Li - Abstract:
- Abstract: Since the coronavirus disease 2019 (COVID‐19) outbreak, the nosocomial infection rate worldwide has been reported high. It is urgent to figure out an affordable way to monitor and alarm nosocomial infection. Carbon dioxide (CO2 ) concentration can reflect the ventilation performance and crowdedness, so CO2 sensors were placed in Beijing Tsinghua Changgung Hospital's fever clinic and emergency department where the nosocomial infection risk was high. Patients' medical records were extracted to figure out their timelines and whereabouts. Based on these, site‐specific CO2 concentration thresholds were calculated by the dilution equation and sites' risk ratios were determined to evaluate ventilation performance. CO2 concentration successfully revealed that the expiratory tracer was poorly diluted in the mechanically ventilated inner spaces, compared to naturally ventilated outer spaces, among all of the monitoring sites that COVID‐19 patients visited. Sufficient ventilation, personal protection, and disinfection measures led to no nosocomial infection in this hospital. The actual outdoor airflow rate per person ( Q c ) during the COVID‐19 patients' presence was estimated for reference using equilibrium analysis. During the stay of single COVID‐19 patient wearing a mask, the minimum Q c value was 15–18 L/(s·person). When the patient was given throat swab sampling, the minimum Q c value was 21 L/(s·person). The Q c value reached 36–42 L/(s·person) thanks toAbstract: Since the coronavirus disease 2019 (COVID‐19) outbreak, the nosocomial infection rate worldwide has been reported high. It is urgent to figure out an affordable way to monitor and alarm nosocomial infection. Carbon dioxide (CO2 ) concentration can reflect the ventilation performance and crowdedness, so CO2 sensors were placed in Beijing Tsinghua Changgung Hospital's fever clinic and emergency department where the nosocomial infection risk was high. Patients' medical records were extracted to figure out their timelines and whereabouts. Based on these, site‐specific CO2 concentration thresholds were calculated by the dilution equation and sites' risk ratios were determined to evaluate ventilation performance. CO2 concentration successfully revealed that the expiratory tracer was poorly diluted in the mechanically ventilated inner spaces, compared to naturally ventilated outer spaces, among all of the monitoring sites that COVID‐19 patients visited. Sufficient ventilation, personal protection, and disinfection measures led to no nosocomial infection in this hospital. The actual outdoor airflow rate per person ( Q c ) during the COVID‐19 patients' presence was estimated for reference using equilibrium analysis. During the stay of single COVID‐19 patient wearing a mask, the minimum Q c value was 15–18 L/(s·person). When the patient was given throat swab sampling, the minimum Q c value was 21 L/(s·person). The Q c value reached 36–42 L/(s·person) thanks to window‐inducted natural ventilation, when two COVID‐19 patients wearing masks shared the same space with other patients or healthcare workers. The CO2 concentration monitoring system proved to be effective in assessing nosocomial infection risk by reflecting real‐time dilution of patients' exhalation. … (more)
- Is Part Of:
- Indoor air. Volume 31:Number 6(2021)
- Journal:
- Indoor air
- Issue:
- Volume 31:Number 6(2021)
- Issue Display:
- Volume 31, Issue 6 (2021)
- Year:
- 2021
- Volume:
- 31
- Issue:
- 6
- Issue Sort Value:
- 2021-0031-0006-0000
- Page Start:
- 1833
- Page End:
- 1842
- Publication Date:
- 2021-06-28
- Subjects:
- Carbon dioxide -- COVID‐19 -- nosocomial infection -- ventilation
Indoor air pollution -- Periodicals
Sick building syndrome -- Periodicals
Ventilation -- Periodicals
613.5 - Journal URLs:
- http://www.blackwell-synergy.com/loi/ina ↗
http://onlinelibrary.wiley.com/journal/10.1111/(ISSN)1600-0668 ↗
http://onlinelibrary.wiley.com/ ↗ - DOI:
- 10.1111/ina.12899 ↗
- Languages:
- English
- ISSNs:
- 0905-6947
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4438.046530
British Library DSC - BLDSS-3PM
British Library STI - ELD Digital store - Ingest File:
- 26356.xml