Induced voltage at the closest pole on parallel line due to direct triggered lightning on 10 kV double circuit distribution line. Issue 4 (2nd January 2023)
- Record Type:
- Journal Article
- Title:
- Induced voltage at the closest pole on parallel line due to direct triggered lightning on 10 kV double circuit distribution line. Issue 4 (2nd January 2023)
- Main Title:
- Induced voltage at the closest pole on parallel line due to direct triggered lightning on 10 kV double circuit distribution line
- Authors:
- Zhao, Yating
Wang, Jianguo
Cai, Li
Li, Quanxin
Fang, Yuqian
Su, Rui
Wang, Shoupeng
Zhou, Mi - Abstract:
- Abstract: In 2019, triggered lightning was used to directly strike phase C of a 1.5 km, 10 kV double‐circuit distribution line in Guangzhou, China, with 2 flashes (13 return strokes) recorded. This paper presents the characteristics of induced voltage at the closest pole on the parallel line. The induced voltage is bipolar, which can be divided into 3 stages: negative increase stage, fast and positive transition stage and slowly returning to zero stage. The positive peak value of phase A voltage ranges from 111.4 to 228.9 kV and that of phase C voltage is from 90.1 to 200.9 kV, corresponding to lightning current from −8.9 to −29.9 kA. The positive peak value of the induced voltage is approximately 3 to 10 times the negative peak value. The negative peak, positive peak and positive 10%–10% duration time of induced voltage show a good linear relationship with the peak value of the return stroke current. There was no flashover occurred during the whole process. The result in this paper can provide data support for numerical simulation and line protection analysis. Abstract : Triggered lightning was used to strike a double circuit distribution line. The voltage waveforms on the other circuit closest to the strike point were analyzed.
- Is Part Of:
- IET generation, transmission & distribution. Volume 17:Issue 4(2023)
- Journal:
- IET generation, transmission & distribution
- Issue:
- Volume 17:Issue 4(2023)
- Issue Display:
- Volume 17, Issue 4 (2023)
- Year:
- 2023
- Volume:
- 17
- Issue:
- 4
- Issue Sort Value:
- 2023-0017-0004-0000
- Page Start:
- 790
- Page End:
- 799
- Publication Date:
- 2023-01-02
- Subjects:
- lightning -- lightning protection -- overvoltage
Electric power production -- Periodicals
Electric power transmission -- Periodicals
Electric power distribution -- Periodicals
621.3105 - Journal URLs:
- http://digital-library.theiet.org/content/journals/iet-gtd ↗
http://ieeexplore.ieee.org/servlet/opac?punumber=4082359 ↗
http://www.ietdl.org/IET-GTD ↗
https://ietresearch.onlinelibrary.wiley.com/journal/17518695 ↗
http://www.theiet.org/ ↗ - DOI:
- 10.1049/gtd2.12706 ↗
- Languages:
- English
- ISSNs:
- 1751-8687
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4363.252540
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 25990.xml