Why do ventilation strategies matter in controlling infectious airborne particles? A comprehensive numerical analysis in isolation ward. (1st March 2023)
- Record Type:
- Journal Article
- Title:
- Why do ventilation strategies matter in controlling infectious airborne particles? A comprehensive numerical analysis in isolation ward. (1st March 2023)
- Main Title:
- Why do ventilation strategies matter in controlling infectious airborne particles? A comprehensive numerical analysis in isolation ward
- Authors:
- Tan, Huiyi
Wong, Keng Yinn
Othman, Mohd Hafiz Dzarfan
Kek, Hong Yee
Nyakuma, Bemgba Bevan
Ho, Wai Shin
Hashim, Haslenda
Wahab, Roswanira Abdul
Sheng, Desmond Daniel Chin Vui
Wahab, Nur Haliza Abdul
Yatim, Ardiyansyah Saad - Abstract:
- Abstract: A proper ventilation strategy in an isolation ward could promote better indoor air quality for the occupants. This could also reduce the risk of immunocompromised patients contracting healthcare-associated infections (HAI) or airborne diseases such as COVID-19, tuberculosis, and measles among others. This study aims to propose and examine appropriate ventilation strategies in a single-patient isolation ward that can reduce particle settlement in patients. A simplified CFD model of the isolation ward was developed and well-validated against established data. An RNG k-ε model and discrete phase model (DPM) were used to simulate airflow and particle transportation. The study examined the airflow and particle dispersion under a baseline case and four proposed ventilation strategies. Results showed that the baseline case study, which used the ceiling-mounted air curtain was insufficient to prevent the particles from dispersing into the vicinity of the patient. Likewise, the dilution effect under the baseline case and case 4 (wall-mounted air supply diffuser) were relatively weak due to the low air change rate (ACH) of 4/hr and 9/hr respectively. The ventilation strategy in case 4 has a negligible effect on reducing the particles (14%) settling on the patient although the ACH in case 4 was 2-times the baseline case. The present finding ascertains that utilising the combination of ceiling-mounted air diffuser and air curtain jet (case 3) results in zero particleAbstract: A proper ventilation strategy in an isolation ward could promote better indoor air quality for the occupants. This could also reduce the risk of immunocompromised patients contracting healthcare-associated infections (HAI) or airborne diseases such as COVID-19, tuberculosis, and measles among others. This study aims to propose and examine appropriate ventilation strategies in a single-patient isolation ward that can reduce particle settlement in patients. A simplified CFD model of the isolation ward was developed and well-validated against established data. An RNG k-ε model and discrete phase model (DPM) were used to simulate airflow and particle transportation. The study examined the airflow and particle dispersion under a baseline case and four proposed ventilation strategies. Results showed that the baseline case study, which used the ceiling-mounted air curtain was insufficient to prevent the particles from dispersing into the vicinity of the patient. Likewise, the dilution effect under the baseline case and case 4 (wall-mounted air supply diffuser) were relatively weak due to the low air change rate (ACH) of 4/hr and 9/hr respectively. The ventilation strategy in case 4 has a negligible effect on reducing the particles (14%) settling on the patient although the ACH in case 4 was 2-times the baseline case. The present finding ascertains that utilising the combination of ceiling-mounted air diffuser and air curtain jet (case 3) results in zero particle settlement on both patient's and the patient's bed. It also reduced 57% of particles in the vicinity of the medical staff's breathing zone compared to the baseline case. Highlights: Ceiling-mounted air curtain was insufficient to prevent the particles from dispersing into the vicinity of the patient. The dilution effect under the ceiling-mounted air curtain and wall-mounted air supply diffuser were relatively weak. Utilising the combination of ceiling-mounted air diffuser and air curtain jet results in zero particle settlement. … (more)
- Is Part Of:
- Building and environment. Volume 231(2023)
- Journal:
- Building and environment
- Issue:
- Volume 231(2023)
- Issue Display:
- Volume 231, Issue 2023 (2023)
- Year:
- 2023
- Volume:
- 231
- Issue:
- 2023
- Issue Sort Value:
- 2023-0231-2023-0000
- Page Start:
- Page End:
- Publication Date:
- 2023-03-01
- Subjects:
- Ventilation strategy -- Healthcare-associated infection -- Isolation ward -- Turbulent airflow -- Particle dispersion
Buildings -- Environmental engineering -- Periodicals
Building -- Research -- Periodicals
Constructions -- Technique de l'environnement -- Périodiques
Electronic journals
696 - Journal URLs:
- http://www.sciencedirect.com/science/journal/03601323 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.buildenv.2023.110048 ↗
- Languages:
- English
- ISSNs:
- 0360-1323
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 2359.355000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 25944.xml