Operational modal analysis of two typical UHV transmission towers: A comparative study by fast Bayesian FFT method. (15th February 2023)
- Record Type:
- Journal Article
- Title:
- Operational modal analysis of two typical UHV transmission towers: A comparative study by fast Bayesian FFT method. (15th February 2023)
- Main Title:
- Operational modal analysis of two typical UHV transmission towers: A comparative study by fast Bayesian FFT method
- Authors:
- Zhu, Y.M.
Sun, Q.
Zhao, C.
Wei, S.T
Yin, Y.
Su, Y.H. - Abstract:
- Highlights: A field measurement of two typical UHV transmission towers is implemented by performing a structural health monitoring (SHM) system. The fast Bayesian FFT method is applied for the dynamic analysis of the UHV transmission towers. The reconstructed signals are used to validate the accuracy approximation of the Bayesian approach. The results can be a reference for wind resistance design of the UHV transmission towers. Abstract: The ultra-high-voltage (UHV) transmission tower is currently the most advanced transmission tower in the world. The UHV transmission line is mainly composed of tangent towers and tension towers with different structural forms. This is interesting from a dynamic point of view, since the two typical structures may behave differently in terms of dynamic characteristics. In this study, a comparative study on operational modal analysis (OMA) of these two typical UHV transmission towers under ambient test is carried out by a fast Bayesian FFT method. Prior to the test, the selected frequency bands of modeling are determined by the sensitivity analysis. A structural health monitoring (SHM) system is installed on the towers during the maintenance period to monitor the acceleration response. The dynamic properties of the towers are obtained by the recently developed fast Bayesian FFT method and compared, the accuracy approximation of the Bayesian approach is verified by frequency domain information reconstruction. Furthermore, the damping ratioHighlights: A field measurement of two typical UHV transmission towers is implemented by performing a structural health monitoring (SHM) system. The fast Bayesian FFT method is applied for the dynamic analysis of the UHV transmission towers. The reconstructed signals are used to validate the accuracy approximation of the Bayesian approach. The results can be a reference for wind resistance design of the UHV transmission towers. Abstract: The ultra-high-voltage (UHV) transmission tower is currently the most advanced transmission tower in the world. The UHV transmission line is mainly composed of tangent towers and tension towers with different structural forms. This is interesting from a dynamic point of view, since the two typical structures may behave differently in terms of dynamic characteristics. In this study, a comparative study on operational modal analysis (OMA) of these two typical UHV transmission towers under ambient test is carried out by a fast Bayesian FFT method. Prior to the test, the selected frequency bands of modeling are determined by the sensitivity analysis. A structural health monitoring (SHM) system is installed on the towers during the maintenance period to monitor the acceleration response. The dynamic properties of the towers are obtained by the recently developed fast Bayesian FFT method and compared, the accuracy approximation of the Bayesian approach is verified by frequency domain information reconstruction. Furthermore, the damping ratio results as well as other voltage levels are compared with different nations codes. It is found that the stiffness of the tension tower is relatively higher than that of the tangent tower. The first-mode damping ratio results of tower in all directions exceeds 2.59% and the vertical cross-arm direction of tension tower reaches 4.54%. The research results can provide a reference for the wind resistance design for UHV transmission tower, and can be used in model updating in the future works. … (more)
- Is Part Of:
- Engineering structures. Volume 277(2023)
- Journal:
- Engineering structures
- Issue:
- Volume 277(2023)
- Issue Display:
- Volume 277, Issue 2023 (2023)
- Year:
- 2023
- Volume:
- 277
- Issue:
- 2023
- Issue Sort Value:
- 2023-0277-2023-0000
- Page Start:
- Page End:
- Publication Date:
- 2023-02-15
- Subjects:
- UHV transmission tower -- Operational modal analysis -- Field vibration test -- Fast Bayesian FFT
Structural engineering -- Periodicals
Structural analysis (Engineering) -- Periodicals
Construction, Technique de la -- Périodiques
Génie parasismique -- Périodiques
Pression du vent -- Périodiques
Earthquake engineering
Structural engineering
Wind-pressure
Periodicals
624.105 - Journal URLs:
- http://www.sciencedirect.com/science/journal/01410296 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.engstruct.2022.115425 ↗
- Languages:
- English
- ISSNs:
- 0141-0296
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3770.032000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 25942.xml