Performance analysis of solar-assisted-geothermal combined cooling, heating, and power (CCHP) systems incorporated with a hydrogen generation subsystem. (15th April 2023)
- Record Type:
- Journal Article
- Title:
- Performance analysis of solar-assisted-geothermal combined cooling, heating, and power (CCHP) systems incorporated with a hydrogen generation subsystem. (15th April 2023)
- Main Title:
- Performance analysis of solar-assisted-geothermal combined cooling, heating, and power (CCHP) systems incorporated with a hydrogen generation subsystem
- Authors:
- Assareh, Ehsanolah
Dejdar, Ali
Ershadi, Ali
Jafarian, Masoud
Mansouri, Mohammadhossein
Salek roshani, Amir
Azish, Ehsan
Saedpanah, Ehsan
Aghajari, Mona
Wang, Xiaolin - Abstract:
- Abstract: In this study, the response surface method (RSM) and transient assessment was used to evaluate the energy and economic performance of a solar-assisted-geothermal combined cooling, heating, and power system (SG-CCHP). The proposed SG-CCHP process consisted of two steam turbines (STs), photovoltaic/thermal (PV/T) collectors, a fuel cell circuit, an absorption chiller, and a heat pump (HP), with battery cells and a hydrogen storage container as the power storage modules. The system's performance was investigated using the TRNSYS modeling tool. The design of experiments (DOE) approach was used to determine the optimal arrangement of the SG-CCHP scheme by controlling the key design factors. A number of simulation scenarios were generated using DOE, and their outcomes were analyzed using RSM. The transient interactions of the controlling design factors on the techno-economic metrics were given after RSM identified the optimal SG-CCHP scheme. The number of PV/T panels, steam turbine capacity, fuel cell power, HP heating capacity and absorption chiller cooling capacity were considered as decision variables. Total electricity consumption (TEU) and auxiliary boiler fuel consumption (ABFU) as indicators of primary energy consumption of the system and predicted average vote (PMV) as an index of thermal comfort of the system and life cycle cost (LCC) as an economic measure to 4 objective functions were selected for optimization. The results indicated that the optimal systemAbstract: In this study, the response surface method (RSM) and transient assessment was used to evaluate the energy and economic performance of a solar-assisted-geothermal combined cooling, heating, and power system (SG-CCHP). The proposed SG-CCHP process consisted of two steam turbines (STs), photovoltaic/thermal (PV/T) collectors, a fuel cell circuit, an absorption chiller, and a heat pump (HP), with battery cells and a hydrogen storage container as the power storage modules. The system's performance was investigated using the TRNSYS modeling tool. The design of experiments (DOE) approach was used to determine the optimal arrangement of the SG-CCHP scheme by controlling the key design factors. A number of simulation scenarios were generated using DOE, and their outcomes were analyzed using RSM. The transient interactions of the controlling design factors on the techno-economic metrics were given after RSM identified the optimal SG-CCHP scheme. The number of PV/T panels, steam turbine capacity, fuel cell power, HP heating capacity and absorption chiller cooling capacity were considered as decision variables. Total electricity consumption (TEU) and auxiliary boiler fuel consumption (ABFU) as indicators of primary energy consumption of the system and predicted average vote (PMV) as an index of thermal comfort of the system and life cycle cost (LCC) as an economic measure to 4 objective functions were selected for optimization. The results indicated that the optimal system significantly reduced its annual life cycle costs, thermal comfort score, total power usage, and auxiliary boiler natural gas usage. The findings also demonstrated that the SG-CCHP system's integration of battery and hydrogen storage components achieved the maximum efficiencies of 90%, 60%, 23%, and 18% for the electrolyzer, fuel cell, PV/T solar collector, and electrical generator, respectively over a year. The optimization results showed that the system cycle cost (LCC) is $514, 188.21 per year, the system comfort coefficient (PMV) is 0.257 per year, the boiler fuel consumption is 46, 271.40 cubic meters per year, and the total electricity consumption is −50, 082.37 kWh per year. Highlights: a solar-assisted-geothermal combined cooling, heating, and power system coupled. Techno-economic perspectives using response surface methodology (RSM). Dynamic approach using the TRNSYS simulation platform. Electrical efficiencies of 90%, 60%, 23%, and 18% over the course of a year. … (more)
- Is Part Of:
- Journal of building engineering. Volume 65(2023)
- Journal:
- Journal of building engineering
- Issue:
- Volume 65(2023)
- Issue Display:
- Volume 65, Issue 2023 (2023)
- Year:
- 2023
- Volume:
- 65
- Issue:
- 2023
- Issue Sort Value:
- 2023-0065-2023-0000
- Page Start:
- Page End:
- Publication Date:
- 2023-04-15
- Subjects:
- Hydrogen generation -- Combined cooling -- Heating -- And power system -- Response surface method -- Energy and economic analysis -- Photovoltaic/thermal solar collectors
Building -- Periodicals
690.05 - Journal URLs:
- http://www.sciencedirect.com/science/journal/23527102 ↗
http://www.sciencedirect.com/ ↗ - DOI:
- 10.1016/j.jobe.2022.105727 ↗
- Languages:
- English
- ISSNs:
- 2352-7102
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 25021.xml