Mal-operation analysis of LCC-HVDC protection schemes in simulation studies due to inaccurate transmission line modelling. Issue 4 (2nd October 2022)
- Record Type:
- Journal Article
- Title:
- Mal-operation analysis of LCC-HVDC protection schemes in simulation studies due to inaccurate transmission line modelling. Issue 4 (2nd October 2022)
- Main Title:
- Mal-operation analysis of LCC-HVDC protection schemes in simulation studies due to inaccurate transmission line modelling
- Authors:
- Marvasti, Farzad Dehghan
Mirzaei, Ahmad - Abstract:
- ABSTRACT: Protection in HVDC transmission lines, considering the significant amount of energy being transferred, has an undeniable importance on integrity of power systems. Due to unavailability of real HVDC transient data for protection studies, accurate modelling of HVDC systems through simulation software is the most practical alternative. One crucial part of a detailed transient simulation study is accurate line modelling, which, if not performed properly, can invalidate the results and conclusions. Therefore, in this study, three of the most accepted line models, namely the frequency-dependent, Bergeron and π -section line models, will be discussed, and their impact on the performance of some of the most accepted HVDC protection methods will be investigated. In comparison to the frequency-dependent line model, which produces the most accurate response, other line models are such inaccurate that their responses in simulation studies are not usable for designing a reliable protection scheme. The simulation study shows that some of the distance or boundary protection methods, designed based on integrating a Bergeron or π -section line model into their studies, can be completely unreliable. The validity of these claims is assessed based on the modified bipolar version of the CIGRE HVDC test system, simulated in the PSCAD/EMTDC software.
- Is Part Of:
- Australian journal of electrical & electronics engineering. Volume 19:Issue 4(2022)
- Journal:
- Australian journal of electrical & electronics engineering
- Issue:
- Volume 19:Issue 4(2022)
- Issue Display:
- Volume 19, Issue 4 (2022)
- Year:
- 2022
- Volume:
- 19
- Issue:
- 4
- Issue Sort Value:
- 2022-0019-0004-0000
- Page Start:
- 407
- Page End:
- 416
- Publication Date:
- 2022-10-02
- Subjects:
- Bergeron line model -- boundary protection -- distance protection -- frequency-dependent line model -- HVDC transmission lines
Electrical engineering -- Periodicals
Electronics -- Periodicals
Periodicals
621.305 - Journal URLs:
- http://www.tandfonline.com/toc/tele20/current ↗
http://search.informit.com.au/search;res=e-library ↗
http://www.tandfonline.com/ ↗ - DOI:
- 10.1080/1448837X.2022.2092997 ↗
- Languages:
- English
- ISSNs:
- 1448-837X
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1807.625000
British Library DSC - BLDSS-3PM
British Library STI - ELD Digital store - Ingest File:
- 24348.xml