Enhancing the flexibility and efficiency of a double-reheat coal-fired power unit by optimizing the steam temperature control: From simulation to application. (25th November 2022)
- Record Type:
- Journal Article
- Title:
- Enhancing the flexibility and efficiency of a double-reheat coal-fired power unit by optimizing the steam temperature control: From simulation to application. (25th November 2022)
- Main Title:
- Enhancing the flexibility and efficiency of a double-reheat coal-fired power unit by optimizing the steam temperature control: From simulation to application
- Authors:
- Wang, Chaoyang
Liu, Zefeng
Fan, Mengyang
Zhao, Yongliang
Liu, Ming
Yan, Junjie - Abstract:
- Highlights: A dynamic model of a thermal power unit coupled with control schemes was developed. Leading signal correction was adopted to optimize the controls of the power unit. Revised control loops can regulate steam and metal temperature more smoothly. Revised control loops can reduce and the efficiency penalty due to spray water. Flexibility and efficiency are co-enhanced by optimizing steam temperature control. Abstract: Flexibility enhancement is crucial for thermal power plants to assist the power grid in accommodating the high penetration of intermittent renewable power. In this study, a new scheme for controlling the steam temperatures of a double-reheat coal-fired power unit is proposed. The scheme uses the leading signal correction of the low-temperature reheater for the control loop regulating the dampers fixed in the fuel gas ducts of the boiler. The scheme was tested using a dynamic model and applied to an in-service double-reheat coal-fired power plant. The results show that both flexibility and efficiency were enhanced when the new control scheme was adopted. The quantity of spray water for the secondary reheat steam could be reduced by 10 %–50 % during the peak-shaving transients with a load cycling rate in the range of 1 %–4 % rated power per minute. The average coal consumption rate decreased by 0.8–1.9 g kW −1 h −1, which accounted for 0.29 %–0.69 % of the thermal efficiency of the power plant. The variation trends of the reheat steam temperatures becameHighlights: A dynamic model of a thermal power unit coupled with control schemes was developed. Leading signal correction was adopted to optimize the controls of the power unit. Revised control loops can regulate steam and metal temperature more smoothly. Revised control loops can reduce and the efficiency penalty due to spray water. Flexibility and efficiency are co-enhanced by optimizing steam temperature control. Abstract: Flexibility enhancement is crucial for thermal power plants to assist the power grid in accommodating the high penetration of intermittent renewable power. In this study, a new scheme for controlling the steam temperatures of a double-reheat coal-fired power unit is proposed. The scheme uses the leading signal correction of the low-temperature reheater for the control loop regulating the dampers fixed in the fuel gas ducts of the boiler. The scheme was tested using a dynamic model and applied to an in-service double-reheat coal-fired power plant. The results show that both flexibility and efficiency were enhanced when the new control scheme was adopted. The quantity of spray water for the secondary reheat steam could be reduced by 10 %–50 % during the peak-shaving transients with a load cycling rate in the range of 1 %–4 % rated power per minute. The average coal consumption rate decreased by 0.8–1.9 g kW −1 h −1, which accounted for 0.29 %–0.69 % of the thermal efficiency of the power plant. The variation trends of the reheat steam temperatures became smooth, and the maximal measured metal temperature decreased by 12 °C. The results can guide the control optimization of modern peak-shaving power plants. … (more)
- Is Part Of:
- Applied thermal engineering. Volume 217(2022)
- Journal:
- Applied thermal engineering
- Issue:
- Volume 217(2022)
- Issue Display:
- Volume 217, Issue 2022 (2022)
- Year:
- 2022
- Volume:
- 217
- Issue:
- 2022
- Issue Sort Value:
- 2022-0217-2022-0000
- Page Start:
- Page End:
- Publication Date:
- 2022-11-25
- Subjects:
- Flexibility and efficiency -- Double-reheat coal-fired power unit -- Peak-shaving transient process -- Control scheme optimization -- Steam temperature control
Heat engineering -- Periodicals
Heating -- Equipment and supplies -- Periodicals
Periodicals
621.40205 - Journal URLs:
- http://www.sciencedirect.com/science/journal/13594311 ↗
http://www.elsevier.com/homepage/elecserv.htt ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.applthermaleng.2022.119240 ↗
- Languages:
- English
- ISSNs:
- 1359-4311
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1580.101000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 23877.xml