Comparative study of upgraded CO2 transcritical air source heat pump systems with different heat sinks. (5th February 2021)
- Record Type:
- Journal Article
- Title:
- Comparative study of upgraded CO2 transcritical air source heat pump systems with different heat sinks. (5th February 2021)
- Main Title:
- Comparative study of upgraded CO2 transcritical air source heat pump systems with different heat sinks
- Authors:
- Yao, Liang
Li, Minxia
Hu, Yusheng
Wang, Qifan
Liu, Xuetao - Abstract:
- Highlights: Three improved CO2 heat pump systems with two compressors are compared at three heat sinks by thermodynamic analysis. Based on five domestic heating regions of China, the economic change of improved CO2 heat pump systems is studied. The most economical system in different application ranges is proposed. Abstract: For improving the coefficient of performance of system for heating, CO2 transcritical heat pump system is upgraded by using two compressors. In this paper, three CO2 transcritical systems with two-compressors (the CO2 cascade system, the CO2 two-stage compression system and the CO2 /CO2 mechanical subcooling system) are discussed and compared with CO2 single-stage compression transcritical heat pump system under three different heat sinks. The three heat sinks are the small temperature difference fan-coil unit, the floor-coil radiator and the traditional designed radiator. And the optimal operation states of three upgraded systems are analyzed. When the thermodynamic performance of CO2 transcritical heat pump system is optimized, the initial investment cost of its equipment often increases and the overall cost will be affected during the life cycle of the equipment. Thus, an objective function that comprehensively considers the initial investment cost and operating cost is defined, and the comparative analysis of four CO2 transcritical heat pump systems is combined meteorological parameters of five typical regions in China for home heating. The resultsHighlights: Three improved CO2 heat pump systems with two compressors are compared at three heat sinks by thermodynamic analysis. Based on five domestic heating regions of China, the economic change of improved CO2 heat pump systems is studied. The most economical system in different application ranges is proposed. Abstract: For improving the coefficient of performance of system for heating, CO2 transcritical heat pump system is upgraded by using two compressors. In this paper, three CO2 transcritical systems with two-compressors (the CO2 cascade system, the CO2 two-stage compression system and the CO2 /CO2 mechanical subcooling system) are discussed and compared with CO2 single-stage compression transcritical heat pump system under three different heat sinks. The three heat sinks are the small temperature difference fan-coil unit, the floor-coil radiator and the traditional designed radiator. And the optimal operation states of three upgraded systems are analyzed. When the thermodynamic performance of CO2 transcritical heat pump system is optimized, the initial investment cost of its equipment often increases and the overall cost will be affected during the life cycle of the equipment. Thus, an objective function that comprehensively considers the initial investment cost and operating cost is defined, and the comparative analysis of four CO2 transcritical heat pump systems is combined meteorological parameters of five typical regions in China for home heating. The results show that under nominal working conditions of three heat sinks, COPs of CO2 cascade system, CO2 two-stage compression system and CO2 /CO2 mechanical sub-cooling system are all increased by more than 10% compared with that of single-stage system and the growth extent of COP increases with the rise of return water temperature of heat sink, but based on the economic analysis, it is implied that CO2 cascade system, CO2 two-stage compression system and CO2 /CO2 mechanical sub-cooling system are not conducive to their application in home heating compared with single-stage system, and more suitable for the situations with low evaporation temperatures and large capacities. The analysis results show that the economy of single-stage system and the three upgraded systems are related to the evaporation temperature and heating capacity. Under the analysis conditions in this paper, CO2 cascade system is the least economical. Single-stage system and the other two upgraded systems can become the most economical system in different application ranges under three heat sink conditions. … (more)
- Is Part Of:
- Applied thermal engineering. Volume 184(2021)
- Journal:
- Applied thermal engineering
- Issue:
- Volume 184(2021)
- Issue Display:
- Volume 184, Issue 2021 (2021)
- Year:
- 2021
- Volume:
- 184
- Issue:
- 2021
- Issue Sort Value:
- 2021-0184-2021-0000
- Page Start:
- Page End:
- Publication Date:
- 2021-02-05
- Subjects:
- CO2 transcritical heat pump -- Mechanical subcooling -- Two-stage compression -- Cascade system -- Thermodynamic and economic analysis -- Different heat sinks
Heat engineering -- Periodicals
Heating -- Equipment and supplies -- Periodicals
Periodicals
621.40205 - Journal URLs:
- http://www.sciencedirect.com/science/journal/13594311 ↗
http://www.elsevier.com/homepage/elecserv.htt ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.applthermaleng.2020.116289 ↗
- Languages:
- English
- ISSNs:
- 1359-4311
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1580.101000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 23766.xml