Estimation of the utility value of unused heat sources for a CO2 network system in Tokyo. (1st July 2021)
- Record Type:
- Journal Article
- Title:
- Estimation of the utility value of unused heat sources for a CO2 network system in Tokyo. (1st July 2021)
- Main Title:
- Estimation of the utility value of unused heat sources for a CO2 network system in Tokyo
- Authors:
- Nagano, Takahiro
Kajita, Jungo
Yoshida, Akira
Amano, Yoshiharu - Abstract:
- Abstract: District heating and cooling (DHC) systems have attracted interest in reducing CO2 emissions. A fifth-generation DHC (5GDHC) system that supplies a heat-transport medium at a temperature close to the ground and uses various unused heat sources is proposed. Meanwhile, some DHC systems installed in Japan are first-generation DHC (1GDHC) systems that use fossil fuels as a heat source. Based on these scenarios, this study focuses on the energy-saving effects of introducing a CO2 network system in Tokyo, which is based on the same concepts as the 5GDHC systems. The purpose of this study is to estimate the utility value of unused heat sources for the CO2 network system. An analytical model is developed that calculates the energy consumption of the system under exogenous conditions, such as those for energy consumers and heat sources. Applying a model to a domestic urban area in Tokyo, where a conventional 1GDHC system was introduced, it was confirmed that for a total head of groundwater of 50 m, river water of 10 m, and sewage water of 10 m, the potential annual CO2 reduction is approximately 5, 000 ton/y compared with the 1GDHC system. These values are feasible in Tokyo, and therefore, this system looks promising. Highlights: Introduction potential of the CO2 network system in Tokyo are evaluated. Utility value of groundwater, sewage water, and river water are estimated. Optimum CO2 temperature is derived for the heat source temperature and heat demand. Groundwater isAbstract: District heating and cooling (DHC) systems have attracted interest in reducing CO2 emissions. A fifth-generation DHC (5GDHC) system that supplies a heat-transport medium at a temperature close to the ground and uses various unused heat sources is proposed. Meanwhile, some DHC systems installed in Japan are first-generation DHC (1GDHC) systems that use fossil fuels as a heat source. Based on these scenarios, this study focuses on the energy-saving effects of introducing a CO2 network system in Tokyo, which is based on the same concepts as the 5GDHC systems. The purpose of this study is to estimate the utility value of unused heat sources for the CO2 network system. An analytical model is developed that calculates the energy consumption of the system under exogenous conditions, such as those for energy consumers and heat sources. Applying a model to a domestic urban area in Tokyo, where a conventional 1GDHC system was introduced, it was confirmed that for a total head of groundwater of 50 m, river water of 10 m, and sewage water of 10 m, the potential annual CO2 reduction is approximately 5, 000 ton/y compared with the 1GDHC system. These values are feasible in Tokyo, and therefore, this system looks promising. Highlights: Introduction potential of the CO2 network system in Tokyo are evaluated. Utility value of groundwater, sewage water, and river water are estimated. Optimum CO2 temperature is derived for the heat source temperature and heat demand. Groundwater is the most favorable in Tokyo from the point of view of CO2 saving. Annual CO2 emissions can be reduced by 40% with respect to the conventional system. … (more)
- Is Part Of:
- Energy. Volume 226(2021)
- Journal:
- Energy
- Issue:
- Volume 226(2021)
- Issue Display:
- Volume 226, Issue 2021 (2021)
- Year:
- 2021
- Volume:
- 226
- Issue:
- 2021
- Issue Sort Value:
- 2021-0226-2021-0000
- Page Start:
- Page End:
- Publication Date:
- 2021-07-01
- Subjects:
- CO2 networks -- District heating and cooling systems -- Distributed heat pump -- Unused energy sources -- Energy conservation
Power resources -- Periodicals
Power (Mechanics) -- Periodicals
Energy consumption -- Periodicals
333.7905 - Journal URLs:
- http://www.elsevier.com/journals ↗
- DOI:
- 10.1016/j.energy.2021.120302 ↗
- Languages:
- English
- ISSNs:
- 0360-5442
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3747.445000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 23582.xml