A new fault detection and fault location method for multi-terminal high voltage direct current of offshore wind farm. (15th June 2018)
- Record Type:
- Journal Article
- Title:
- A new fault detection and fault location method for multi-terminal high voltage direct current of offshore wind farm. (15th June 2018)
- Main Title:
- A new fault detection and fault location method for multi-terminal high voltage direct current of offshore wind farm
- Authors:
- Li, Jianwei
Yang, Qingqing
Mu, Hao
Le Blond, Simon
He, Hongwen - Abstract:
- Highlights: This paper presented the solution to promote the HVDC system for offshore wind farm. A novel fault detection, classification and location for the MTDC is proposed. The new method is fault resistance independent so that to avoid high fault impedance effects. A three-terminal HVDC test system of offshore wind farm is simulated including converter control. Abstract: This paper proposes a novel protection scheme for multi-terminal High Voltage Direct Current (MTDC) systems incorporating offshore wind farm based on high-frequency components detected from the fault current signal. This method can accurately detect the fault on each line and classify the fault types. Using the post-fault current time series, both single-ended measurements (detection and classification) and double-end measurements (location), the frequency spectrum is generated to measure the gaps between the contiguous peak frequencies giving a robust and comprehensive scheme. Unlike the previous travelling wave based methods, which must identify the travelling wavefront and require a high sampling rate, the new gap-based approach is able to give accurate fault detection and fault location using any appropriate range of post-fault signals. Furthermore, the proposed method is fault resistance independent and thus even a very high fault impedance has no effect on the fault location detection. By immediately tripping the faults, the fault-caused disturbance to the offshore wind farm is minimized. AHighlights: This paper presented the solution to promote the HVDC system for offshore wind farm. A novel fault detection, classification and location for the MTDC is proposed. The new method is fault resistance independent so that to avoid high fault impedance effects. A three-terminal HVDC test system of offshore wind farm is simulated including converter control. Abstract: This paper proposes a novel protection scheme for multi-terminal High Voltage Direct Current (MTDC) systems incorporating offshore wind farm based on high-frequency components detected from the fault current signal. This method can accurately detect the fault on each line and classify the fault types. Using the post-fault current time series, both single-ended measurements (detection and classification) and double-end measurements (location), the frequency spectrum is generated to measure the gaps between the contiguous peak frequencies giving a robust and comprehensive scheme. Unlike the previous travelling wave based methods, which must identify the travelling wavefront and require a high sampling rate, the new gap-based approach is able to give accurate fault detection and fault location using any appropriate range of post-fault signals. Furthermore, the proposed method is fault resistance independent and thus even a very high fault impedance has no effect on the fault location detection. By immediately tripping the faults, the fault-caused disturbance to the offshore wind farm is minimized. A three-terminal voltage sourced converter HVDC (VSC-HVDC) system connection of offshore wind farm is modelled in PSCAD/EMTDC (Power Systems Computer Aided Design/Electro-Magnetic Transients including DC) software, which is used for obtaining the fault current data for the transmission line terminal. The algorithm is verified by studying a range of cases, by varying the fault resistance fault locations and also including external faults. The results show that the proposed method gives an accurate and reliable fault detection, classification and location on the test MTDC system. … (more)
- Is Part Of:
- Applied energy. Volume 220(2018)
- Journal:
- Applied energy
- Issue:
- Volume 220(2018)
- Issue Display:
- Volume 220, Issue 2018 (2018)
- Year:
- 2018
- Volume:
- 220
- Issue:
- 2018
- Issue Sort Value:
- 2018-0220-2018-0000
- Page Start:
- 13
- Page End:
- 20
- Publication Date:
- 2018-06-15
- Subjects:
- Fault location -- Frequency spectrum -- Offshore wind farm -- Transmission line -- VSC-HVDC system
Power (Mechanics) -- Periodicals
Energy conservation -- Periodicals
Energy conversion -- Periodicals
621.042 - Journal URLs:
- http://www.sciencedirect.com/science/journal/03062619 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.apenergy.2018.03.044 ↗
- Languages:
- English
- ISSNs:
- 0306-2619
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1572.300000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: