A novel defouling initiation method for a space cooling ASHP unit based on its measurable characteristic ambient and operating temperatures. (August 2019)
- Record Type:
- Journal Article
- Title:
- A novel defouling initiation method for a space cooling ASHP unit based on its measurable characteristic ambient and operating temperatures. (August 2019)
- Main Title:
- A novel defouling initiation method for a space cooling ASHP unit based on its measurable characteristic ambient and operating temperatures
- Authors:
- Li, Zhaoyang
Wang, Wei
Sun, Yuying
Liu, Jingdong
Deng, Shiming
Liang, Shimin - Abstract:
- Highlights: A novel method for defouling fouled outdoor coils in ASHPs has been developed. The method is based on three directly measurable operating temperatures. Further field studies to verify the method's applicability were carried out. The method provided an accurate and convenient way for defouling initiation. Abstract: Air source heat pumps (ASHPs) have been widely used for space cooling in recent years. When a space cooling ASHP unit is operated in an ambience with poor air quality, fouling of its outdoor coil can be easily built up, leading to a significant drop in the operating efficiency and output cooling capacity of the ASHP unit. Therefore, as a follow-up to a previous related study, a study to develop a novel defouling initiation method for the fouled outdoor coil in a space cooling ASHP unit based on its measurable characteristic ambient and operating temperatures has been carried out and the study results are reported in this paper. Firstly, a characteristic parameter of TTT, which can be evaluated based on ambient air Temperature, outdoor coil metal surface Temperature and outdoor coil outlet air Temperature, is defined. Secondly, the development of the novel defouling initiation method is detailed. Finally, further field comparative studies using the developed novel defouling initiation method have been carried out, and the study results demonstrated that the novel defouling initiation method can provide an accurate and convenient way to initiate defoulingHighlights: A novel method for defouling fouled outdoor coils in ASHPs has been developed. The method is based on three directly measurable operating temperatures. Further field studies to verify the method's applicability were carried out. The method provided an accurate and convenient way for defouling initiation. Abstract: Air source heat pumps (ASHPs) have been widely used for space cooling in recent years. When a space cooling ASHP unit is operated in an ambience with poor air quality, fouling of its outdoor coil can be easily built up, leading to a significant drop in the operating efficiency and output cooling capacity of the ASHP unit. Therefore, as a follow-up to a previous related study, a study to develop a novel defouling initiation method for the fouled outdoor coil in a space cooling ASHP unit based on its measurable characteristic ambient and operating temperatures has been carried out and the study results are reported in this paper. Firstly, a characteristic parameter of TTT, which can be evaluated based on ambient air Temperature, outdoor coil metal surface Temperature and outdoor coil outlet air Temperature, is defined. Secondly, the development of the novel defouling initiation method is detailed. Finally, further field comparative studies using the developed novel defouling initiation method have been carried out, and the study results demonstrated that the novel defouling initiation method can provide an accurate and convenient way to initiate defouling of the fouled outdoor coil in an ASHP unit at a reasonable defouling frequency to ensure its best possible operating performances. … (more)
- Is Part Of:
- International journal of refrigeration. Volume 104(2019)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 104(2019)
- Issue Display:
- Volume 104, Issue 2019 (2019)
- Year:
- 2019
- Volume:
- 104
- Issue:
- 2019
- Issue Sort Value:
- 2019-0104-2019-0000
- Page Start:
- 171
- Page End:
- 179
- Publication Date:
- 2019-08
- Subjects:
- Fouling -- Defouling initiation -- ASHP -- Characteristic parameter -- Field study
Encrassement -- Déclenchement du désencrassement -- Pompe à chaleur aérothermique -- Paramètre caractéristique -- Étude de terrain
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2019.03.039 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: