A spatiotemporal indirect evaporative cooler enabled by transiently interceding water mist. (15th February 2021)
- Record Type:
- Journal Article
- Title:
- A spatiotemporal indirect evaporative cooler enabled by transiently interceding water mist. (15th February 2021)
- Main Title:
- A spatiotemporal indirect evaporative cooler enabled by transiently interceding water mist
- Authors:
- Shahzad, Muhammad Wakil
Lin, Jie
Xu, Ben Bin
Dala, Laurent
Chen, Qian
Burhan, Muhammad
Sultan, Muhammad
Worek, William
Ng, Kim Choon - Abstract:
- Abstract: The building sector consumes around half of the global energy produced and air-conditioning processes guzzle over 55% of building sector energy. The conventional refrigerant-based chillers, covering over 90% of the current cooling market, are not only energy-intensive but also have high ozone depletion and global warming potentials. Indirect evaporative coolers were introduced but they were difficult to commercialize due to their practical lower achievable temperature limits. All existing indirect evaporative coolers use hydrophilic interface to provide wet surfaces for evaporative potential. These hydrophilic surfaces not only increase heat transfer resistance but also provide excellent conditions, wet and damp surface, for mold formation. The treatment of mold is almost impossible as the height of the channel is only 3–5 mm and the fungus can be dangerous to health. Therefore, we proposed an innovative indirect evaporative cooling cycle in which there are no hydrophilic surfaces inside the system. The humidification of the working air is carried out before it is introduced into the wet channel. Also, the interface between dry and wet channel is only a thin aluminium foil that boosts heat transfer from supply air to working air in the transverse direction. A generic cell of 1800 mm long and 280 mm wide can produce 182.5 W cooling capacity. The measured coefficient of performance and effectiveness are 45 and 80% respectively for sensible cooling. This basicAbstract: The building sector consumes around half of the global energy produced and air-conditioning processes guzzle over 55% of building sector energy. The conventional refrigerant-based chillers, covering over 90% of the current cooling market, are not only energy-intensive but also have high ozone depletion and global warming potentials. Indirect evaporative coolers were introduced but they were difficult to commercialize due to their practical lower achievable temperature limits. All existing indirect evaporative coolers use hydrophilic interface to provide wet surfaces for evaporative potential. These hydrophilic surfaces not only increase heat transfer resistance but also provide excellent conditions, wet and damp surface, for mold formation. The treatment of mold is almost impossible as the height of the channel is only 3–5 mm and the fungus can be dangerous to health. Therefore, we proposed an innovative indirect evaporative cooling cycle in which there are no hydrophilic surfaces inside the system. The humidification of the working air is carried out before it is introduced into the wet channel. Also, the interface between dry and wet channel is only a thin aluminium foil that boosts heat transfer from supply air to working air in the transverse direction. A generic cell of 1800 mm long and 280 mm wide can produce 182.5 W cooling capacity. The measured coefficient of performance and effectiveness are 45 and 80% respectively for sensible cooling. This basic information of the proposed innovative indirect evaporative cooling system can be used to design a commercial unit as the total capacity is based on number of generic cells. Highlights: Decoupling of sensible and latent load is the key for sustainable cooling. The proposed water droplet intervened IEC system has the best performance. Innovative IEC design can achieve new level of performance, COP 45 for cooling only. The overall COP 10 is achievable with dehumidification system COP around 5. Thin aluminum foil interface and outside humidification of working air is the key for robust operation. … (more)
- Is Part Of:
- Energy. Volume 217(2021)
- Journal:
- Energy
- Issue:
- Volume 217(2021)
- Issue Display:
- Volume 217, Issue 2021 (2021)
- Year:
- 2021
- Volume:
- 217
- Issue:
- 2021
- Issue Sort Value:
- 2021-0217-2021-0000
- Page Start:
- Page End:
- Publication Date:
- 2021-02-15
- Subjects:
- Air-conditioning -- Chillers -- Evaporative cooler -- Coefficient of performance
Power resources -- Periodicals
Power (Mechanics) -- Periodicals
Energy consumption -- Periodicals
333.7905 - Journal URLs:
- http://www.elsevier.com/journals ↗
- DOI:
- 10.1016/j.energy.2020.119352 ↗
- Languages:
- English
- ISSNs:
- 0360-5442
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3747.445000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 22688.xml