Drop-in analysis of R450A and R513A as low-GWP alternatives to R134a in a water-to-water heat pump. (March 2022)
- Record Type:
- Journal Article
- Title:
- Drop-in analysis of R450A and R513A as low-GWP alternatives to R134a in a water-to-water heat pump. (March 2022)
- Main Title:
- Drop-in analysis of R450A and R513A as low-GWP alternatives to R134a in a water-to-water heat pump
- Authors:
- Molinaroli, Luca
Lucchini, Andrea
Colombo, Luigi Pietro Maria - Abstract:
- Highlights: Drop-in comparison of R134a, R450A and R513A. R450A heating capacity is within − 15.02 % and − 6.59 % compared to that of R134a. R450A COP is within − 2.48 % and + 2.99 % with respect to that of R134a. R513A heating capacity is within − 8.78 % and + 3.16 % compared to that of R134a. R513A COP is within − 7.48 % and 2.22% with respect to that of R134a. Abstract: This paper discusses the results of an experimental analysis of the use of R450A and R513A as drop-in alternatives to R134a in a water-to-water heat pump. The heat pump is tested setting the rotational frequency of the compressor shaft, the vapour superheating at the evaporator outlet and the mass flow rates and temperatures of the secondary fluids at the heat exchangers outlets to the desired conditions. Compared to R134a, the use of R450A leads to a capacity reduction, that lays in the range 6.59% to 15.02%, and to a COP variation, that is within the range − 2.48% to +2.99%, whereas with R513A the variations of the heating capacity and COP lay in the range − 8.78% to +3.16% and − 7.48% to +2.22% respectively. The increase in the rotational frequency of the compressor shaft to bring the heating capacity back to the R134a values is discussed too. The required increase is in the range 10% to 16% with R450A and 2% to 8% with R513A, but a COP reduction in the range 0.14% to 5.22% with the former refrigerant and 2.34% to 6.48% with the latter consequently arises.
- Is Part Of:
- International journal of refrigeration. Volume 135(2022)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 135(2022)
- Issue Display:
- Volume 135, Issue 2022 (2022)
- Year:
- 2022
- Volume:
- 135
- Issue:
- 2022
- Issue Sort Value:
- 2022-0135-2022-0000
- Page Start:
- 139
- Page End:
- 147
- Publication Date:
- 2022-03
- Subjects:
- COP -- Heat pump -- Heating capacity -- R450A -- R513A
COP -- Pompe à chaleur -- Puissance de chauffage -- R450A -- R513A
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2021.12.007 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit