Critical evaluation of the thermal performance analysis of a new cooling tower prototype. (August 2022)
- Record Type:
- Journal Article
- Title:
- Critical evaluation of the thermal performance analysis of a new cooling tower prototype. (August 2022)
- Main Title:
- Critical evaluation of the thermal performance analysis of a new cooling tower prototype
- Authors:
- Navarro, P.
Ruiz, J.
Hernández, M.
Kaiser, A.S.
Lucas, M. - Abstract:
- Abstract: This paper presents a critical evaluation of the thermal performance analysis of the inverted cooling tower, which was conceived as a new cooling tower prototype that prevents the dispersion of pollutants to the atmosphere during its operation. The device can be classified as a mechanical forced draft, counterflow-parallel flow cooling tower. The combination of the Merkel and Poppe methods of analysis and the counterflow, parallel and counterflow/parallel flow arrangements has been discussed, for a total of 5 different approaches. The Poppe method for thermal performance prediction reports higher Merkel numbers than the Merkel method: from 3.84% to 6.64%. A higher Merkel number is obtained for the parallel arrangement compared to counterflow to achieve the same cooling. Differences from 1.12% to 12.19% are observed for the range of tested water-to-air mass flow ratios. The rigorous method that uses the Poppe theory and combines counterflow and parallel flow arrangements (main novelty of this paper) is recommended to evaluate the thermal performance. Not only it provides the best predictions for the outlet water and air temperatures (0.44 °C difference for the water prediction and 0.74 °C difference for the air) but it is a good approximation of the complex underlying physics of the problem and the state of the outlet air is accurately determined. Highlights: A critical evaluation of the performance of a novel cooling tower was conducted. The Poppe theory combiningAbstract: This paper presents a critical evaluation of the thermal performance analysis of the inverted cooling tower, which was conceived as a new cooling tower prototype that prevents the dispersion of pollutants to the atmosphere during its operation. The device can be classified as a mechanical forced draft, counterflow-parallel flow cooling tower. The combination of the Merkel and Poppe methods of analysis and the counterflow, parallel and counterflow/parallel flow arrangements has been discussed, for a total of 5 different approaches. The Poppe method for thermal performance prediction reports higher Merkel numbers than the Merkel method: from 3.84% to 6.64%. A higher Merkel number is obtained for the parallel arrangement compared to counterflow to achieve the same cooling. Differences from 1.12% to 12.19% are observed for the range of tested water-to-air mass flow ratios. The rigorous method that uses the Poppe theory and combines counterflow and parallel flow arrangements (main novelty of this paper) is recommended to evaluate the thermal performance. Not only it provides the best predictions for the outlet water and air temperatures (0.44 °C difference for the water prediction and 0.74 °C difference for the air) but it is a good approximation of the complex underlying physics of the problem and the state of the outlet air is accurately determined. Highlights: A critical evaluation of the performance of a novel cooling tower was conducted. The Poppe theory combining parallel/countercurrent flow arrangements is suggested. The method predictions are confident: less than 2% for water and air temperatures. The Poppe theory reports results 3.76% and 6.67% higher than the Merkel theory. Parallel configuration provides up to 12.26% higher Merkel number than counterflow. … (more)
- Is Part Of:
- Applied thermal engineering. Volume 213(2022)
- Journal:
- Applied thermal engineering
- Issue:
- Volume 213(2022)
- Issue Display:
- Volume 213, Issue 2022 (2022)
- Year:
- 2022
- Volume:
- 213
- Issue:
- 2022
- Issue Sort Value:
- 2022-0213-2022-0000
- Page Start:
- Page End:
- Publication Date:
- 2022-08
- Subjects:
- Cooling tower -- Thermal performance -- Flow arrangement -- Merkel -- Poppe
Heat engineering -- Periodicals
Heating -- Equipment and supplies -- Periodicals
Periodicals
621.40205 - Journal URLs:
- http://www.sciencedirect.com/science/journal/13594311 ↗
http://www.elsevier.com/homepage/elecserv.htt ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.applthermaleng.2022.118719 ↗
- Languages:
- English
- ISSNs:
- 1359-4311
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1580.101000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 22113.xml