Comparative analysis of the energy efficiency of air-conditioner and variable refrigerant flow systems in residential buildings in the Yangtze River region. (1st September 2022)
- Record Type:
- Journal Article
- Title:
- Comparative analysis of the energy efficiency of air-conditioner and variable refrigerant flow systems in residential buildings in the Yangtze River region. (1st September 2022)
- Main Title:
- Comparative analysis of the energy efficiency of air-conditioner and variable refrigerant flow systems in residential buildings in the Yangtze River region
- Authors:
- Xiao, Hansong
Yang, Zixu
Shi, Wenxing
Wang, Baolong
Li, Baizhan
Song, Qiang
Li, Jinbo
Xu, Zhenkun - Abstract:
- Abstract: Two types of air-conditioning systems, named as room air conditioners (RAC) and multi-connected air-conditioners (variable refrigerant flow (VRF) systems) have become popular heating and cooling facilities for residential buildings featured with 'part-time-part-space' operation characteristics in the Yangtze River region. However, the research on the energy efficiency of these two systems in residential buildings is currently lacking. Based on the actual measured air-conditioning operation hours and demand characteristics, this study analyzed the annual operation performance of the two systems by modelling and simulation. In addition, a field test of twelve RACs and five VRFs in residential buildings was conducted in the Yangtze River region, showing the annual performance factors of VRFs and RACs ranged from 3.7 to 5.3 kWh·kWh −1 and 3.0 to 4.6 kWh·kWh −1, respectively. It is found that for the same operation hours and the total cooling capacity of VRF systems RACs, the VRF has low energy efficiency at low load ratios (generally less than 25%); which is the key barrier to its application in residential buildings in the Yangtze River region. It is suggested the RAC is the appropriate solution for heating and cooling a residential building with a 'part-time-part-space' operation mode as it is more energy-efficient. New advanced technologies for VRF systems are expected to be developed in order to adapt the part-load operation mode to achieve high energy efficiency.Abstract: Two types of air-conditioning systems, named as room air conditioners (RAC) and multi-connected air-conditioners (variable refrigerant flow (VRF) systems) have become popular heating and cooling facilities for residential buildings featured with 'part-time-part-space' operation characteristics in the Yangtze River region. However, the research on the energy efficiency of these two systems in residential buildings is currently lacking. Based on the actual measured air-conditioning operation hours and demand characteristics, this study analyzed the annual operation performance of the two systems by modelling and simulation. In addition, a field test of twelve RACs and five VRFs in residential buildings was conducted in the Yangtze River region, showing the annual performance factors of VRFs and RACs ranged from 3.7 to 5.3 kWh·kWh −1 and 3.0 to 4.6 kWh·kWh −1, respectively. It is found that for the same operation hours and the total cooling capacity of VRF systems RACs, the VRF has low energy efficiency at low load ratios (generally less than 25%); which is the key barrier to its application in residential buildings in the Yangtze River region. It is suggested the RAC is the appropriate solution for heating and cooling a residential building with a 'part-time-part-space' operation mode as it is more energy-efficient. New advanced technologies for VRF systems are expected to be developed in order to adapt the part-load operation mode to achieve high energy efficiency. This study contributes to providing evidence for the decision-making of RAC and VRF systems for policymakers, and building and engineering designers in the context of energy efficiency for the region. Highlights: Analysis of energy performance of RAC and VRF system in residential buildings. Tested 12 RACs and 5 VRFs in real buildings in the Yangtze River region. Identified low load ratio as the key factor restricting the application of residential VRFs. … (more)
- Is Part Of:
- Journal of building engineering. Volume 55(2022)
- Journal:
- Journal of building engineering
- Issue:
- Volume 55(2022)
- Issue Display:
- Volume 55, Issue 2022 (2022)
- Year:
- 2022
- Volume:
- 55
- Issue:
- 2022
- Issue Sort Value:
- 2022-0055-2022-0000
- Page Start:
- Page End:
- Publication Date:
- 2022-09-01
- Subjects:
- Room air conditioner -- Multi-connected air conditioner -- Residential variable refrigerant flow system -- Yangtze River region
Building -- Periodicals
690.05 - Journal URLs:
- http://www.sciencedirect.com/science/journal/23527102 ↗
http://www.sciencedirect.com/ ↗ - DOI:
- 10.1016/j.jobe.2022.104644 ↗
- Languages:
- English
- ISSNs:
- 2352-7102
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 21794.xml