Analyses of the improvement of subway station thermal environment in northern severe cold regions. (1st October 2018)
- Record Type:
- Journal Article
- Title:
- Analyses of the improvement of subway station thermal environment in northern severe cold regions. (1st October 2018)
- Main Title:
- Analyses of the improvement of subway station thermal environment in northern severe cold regions
- Authors:
- Ma, Jiangyan
Zhang, Xin
Li, Angui
Deng, Baoshun
Lv, Wenchao
Guo, Yongzhen
Zhang, Wenrong
Huang, Lin - Abstract:
- Abstract: Currently, subway lines are being increasingly constructed in the northern severe cold regions of China. The average ambient temperature in this region is below −10 °C during winter. Therefore, the extreme climate and piston effect impose challenges for designers for enhancing the thermal environment of a metro station in severe cold season. In this study, one-dimensional modelling is developed using the IDA Simulation Environment (IDA) based on an actual metro line, and the results are validated by experimental data. Moreover, the thermal environment of a typical metro station in the control group, two traditional optimisation measures, and one new method are investigated in severe cold regions. The results indicate that the primary heat loss during winter is attributed to the cold air invasion caused by the piston effect from the entrances. The addition of a warm-air curtain individually at the entrance may not effectively prevent the intrusion of cold air. Furthermore, adding a door curtain can reduce the inlet air volume of the entrance, but reduce the outlet air volume of the entrance. Thus, the heat of the train brake cannot be effectively utilised to improve the station temperature. In addition, one new method using the piston wind principle was presented, and it can effectively prevent the cold wind and more effectively utilise the train braking energy to improve the temperature of the metro station. It serves as a guideline for subway environmental controlAbstract: Currently, subway lines are being increasingly constructed in the northern severe cold regions of China. The average ambient temperature in this region is below −10 °C during winter. Therefore, the extreme climate and piston effect impose challenges for designers for enhancing the thermal environment of a metro station in severe cold season. In this study, one-dimensional modelling is developed using the IDA Simulation Environment (IDA) based on an actual metro line, and the results are validated by experimental data. Moreover, the thermal environment of a typical metro station in the control group, two traditional optimisation measures, and one new method are investigated in severe cold regions. The results indicate that the primary heat loss during winter is attributed to the cold air invasion caused by the piston effect from the entrances. The addition of a warm-air curtain individually at the entrance may not effectively prevent the intrusion of cold air. Furthermore, adding a door curtain can reduce the inlet air volume of the entrance, but reduce the outlet air volume of the entrance. Thus, the heat of the train brake cannot be effectively utilised to improve the station temperature. In addition, one new method using the piston wind principle was presented, and it can effectively prevent the cold wind and more effectively utilise the train braking energy to improve the temperature of the metro station. It serves as a guideline for subway environmental control system (ECS) design. Highlights: The heat loss at subway station is mainly attributed to air invasion caused by the piston effect. The warm-air curtains method may not effectively prevent the intrusion of cold air. The door curtains in the entrances may reduce the heat utilization of the train-braking. A new local component is proposed to improve the station thermal environment. … (more)
- Is Part Of:
- Building and environment. Volume 143(2018)
- Journal:
- Building and environment
- Issue:
- Volume 143(2018)
- Issue Display:
- Volume 143, Issue 2018 (2018)
- Year:
- 2018
- Volume:
- 143
- Issue:
- 2018
- Issue Sort Value:
- 2018-0143-2018-0000
- Page Start:
- 579
- Page End:
- 590
- Publication Date:
- 2018-10-01
- Subjects:
- Subway station -- Piston effect -- Thermal environment -- Severe cold regions -- PBD
Buildings -- Environmental engineering -- Periodicals
Building -- Research -- Periodicals
Constructions -- Technique de l'environnement -- Périodiques
Electronic journals
696 - Journal URLs:
- http://www.sciencedirect.com/science/journal/03601323 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.buildenv.2018.07.039 ↗
- Languages:
- English
- ISSNs:
- 0360-1323
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 2359.355000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 20791.xml