Experimental investigation of human tenability and sprinkler protection in hospital room fires. (4th August 2020)
- Record Type:
- Journal Article
- Title:
- Experimental investigation of human tenability and sprinkler protection in hospital room fires. (4th August 2020)
- Main Title:
- Experimental investigation of human tenability and sprinkler protection in hospital room fires
- Authors:
- Hostikka, Simo
Veikkanen, Eetu
Hakkarainen, Tuula
Kajolinna, Tuula - Other Names:
- Klippel Andrea guestEditor.
Meacham Brian guestEditor.
Wang Yi guestEditor. - Abstract:
- Summary: The effectiveness of sprinklers in protecting hospital patients in the room of fire origin was investigated by 14 experiments with a residential‐grade sprinkler system, and by two free‐burns. The fire load was UL 1626 corner fire. Tenability conditions were evaluated for the UL 1626 corner fire using gas temperature and species concentration measurements, and by calculating the fractional effective dose (FED) and fractional irritant concentration (FIC) with the comprehensive model of Purser and a more simplified method of ISO 13571. In the sprinklered tests, the average FED at 15 minutes was 0.8 ± 1 with 95% confidence, when using the Purser's method, and 0.2 ± 0.2 with ISO 13571. The difference was mainly caused by the assumption in the Purser's method that all NOx gases behave like NO2 . Ignoring the NO contributions decreased the Purser's FED values very close to those of ISO 13571. In nonsprinklered tests, the FED and FIC values indicated definite incapacitation and possibly death 3 minutes after ignition. The sprinklers effectively increase the possibility of surviving, but the toxic effects may still be dangerous. In hospital and health care environments, many of the exposed persons may have lower‐than‐average tolerance.
- Is Part Of:
- Fire and materials. Volume 45:Number 6(2021)
- Journal:
- Fire and materials
- Issue:
- Volume 45:Number 6(2021)
- Issue Display:
- Volume 45, Issue 6 (2021)
- Year:
- 2021
- Volume:
- 45
- Issue:
- 6
- Issue Sort Value:
- 2021-0045-0006-0000
- Page Start:
- 823
- Page End:
- 832
- Publication Date:
- 2020-08-04
- Subjects:
- experiment -- FED -- fire suppression -- fire toxicity -- hospital fire -- sprinklers
Fire-testing -- Periodicals
Fire -- Periodicals
Materials -- Periodicals
620.11217 - Journal URLs:
- http://www3.interscience.wiley.com/cgi-bin/jhome/109607601 ↗
http://www3.interscience.wiley.com/cgi-bin/jhome/3189 ↗
http://onlinelibrary.wiley.com/ ↗ - DOI:
- 10.1002/fam.2893 ↗
- Languages:
- English
- ISSNs:
- 0308-0501
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3930.250000
British Library DSC - BLDSS-3PM
British Library STI - ELD Digital store - Ingest File:
- 19354.xml