Comparison on cooling performance of pre-cooled natural draft dry cooling towers using nozzles spray and wet medium. (October 2021)
- Record Type:
- Journal Article
- Title:
- Comparison on cooling performance of pre-cooled natural draft dry cooling towers using nozzles spray and wet medium. (October 2021)
- Main Title:
- Comparison on cooling performance of pre-cooled natural draft dry cooling towers using nozzles spray and wet medium
- Authors:
- Miao, Jiayu
He, Suoying
Lu, Yuanwei
Wu, Yuting
Wu, Xuehong
Zhang, Guanhong
Gao, Ming
Geng, Zhe
Zhang, Shuzhen - Abstract:
- Abstract: Evaporative pre-cooling technology improves the cooling performance of natural draft dry cooling towers (NDDCTs) by introducing a certain amount of water into the air entrance. This paper compares the effects of different evaporative pre-cooling systems (i.e., normal wet-medium arrangement, A-frame wet-medium arrangement and nozzle spray) on the cooling performance of a 167 m high NDDCT. Based on the meteorological data of Naomao lake in Xinjiang in 2015, two MATLAB programs were developed for case studies. This study finds all the evaporative pre-cooling systems can improve the NDDCT's cooling performance in high temperature period. In non-high temperature period, the NDDCT's performance improvement is unremarkable, and the NDDCT's cooling performance even deteriorates in the case of evaporative pre-cooling using wet medium. In the hottest month of July, the water outlet temperatures of the NDDCT pre-cooled with normal wet-medium arrangement, A-frame wet-medium arrangement and nozzle spray drop 3.2 K, 3.5 K and 3.3 K, respectively when compared with no pre-cooling counterpart. The annual average water consumption values are 39.0 kg/s, 56.4 kg/s and 124.1 kg/s, respectively. Considering all the year around performance improvement, it is suggested to use nozzle spray pre-cooling system while intermittent operation or certain-time period operation should be considered to save water. Graphical abstract: Image 1 Highlights: Two MATLAB programs were developed for caseAbstract: Evaporative pre-cooling technology improves the cooling performance of natural draft dry cooling towers (NDDCTs) by introducing a certain amount of water into the air entrance. This paper compares the effects of different evaporative pre-cooling systems (i.e., normal wet-medium arrangement, A-frame wet-medium arrangement and nozzle spray) on the cooling performance of a 167 m high NDDCT. Based on the meteorological data of Naomao lake in Xinjiang in 2015, two MATLAB programs were developed for case studies. This study finds all the evaporative pre-cooling systems can improve the NDDCT's cooling performance in high temperature period. In non-high temperature period, the NDDCT's performance improvement is unremarkable, and the NDDCT's cooling performance even deteriorates in the case of evaporative pre-cooling using wet medium. In the hottest month of July, the water outlet temperatures of the NDDCT pre-cooled with normal wet-medium arrangement, A-frame wet-medium arrangement and nozzle spray drop 3.2 K, 3.5 K and 3.3 K, respectively when compared with no pre-cooling counterpart. The annual average water consumption values are 39.0 kg/s, 56.4 kg/s and 124.1 kg/s, respectively. Considering all the year around performance improvement, it is suggested to use nozzle spray pre-cooling system while intermittent operation or certain-time period operation should be considered to save water. Graphical abstract: Image 1 Highlights: Two MATLAB programs were developed for case studies of a 167 m high NDDCT. Evaporative pre-cooling systems can improve NDDCT's performance in hot period. Water exit temperature of NDDCT pre-cooled using nozzle spray drops 3.3 K in July. Nozzle spray pre-cooling system is suggested for NDDCT's performance improvement. … (more)
- Is Part Of:
- Case studies in thermal engineering. Volume 27(2021)
- Journal:
- Case studies in thermal engineering
- Issue:
- Volume 27(2021)
- Issue Display:
- Volume 27, Issue 2021 (2021)
- Year:
- 2021
- Volume:
- 27
- Issue:
- 2021
- Issue Sort Value:
- 2021-0027-2021-0000
- Page Start:
- Page End:
- Publication Date:
- 2021-10
- Subjects:
- Natural draft dry cooling tower (NDDCT) -- Evaporative pre-cooling -- Wet medium -- Nozzle spray -- Cooling performance
Heat engineering -- Case studies -- Periodicals
621.40205 - Journal URLs:
- http://www.sciencedirect.com/science/journal/2214157X/ ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.csite.2021.101274 ↗
- Languages:
- English
- ISSNs:
- 2214-157X
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 18509.xml