Study on response characteristics of grid‐side converter controller of PMSG to sub‐synchronous frequency component. Issue 7 (30th May 2017)
- Record Type:
- Journal Article
- Title:
- Study on response characteristics of grid‐side converter controller of PMSG to sub‐synchronous frequency component. Issue 7 (30th May 2017)
- Main Title:
- Study on response characteristics of grid‐side converter controller of PMSG to sub‐synchronous frequency component
- Authors:
- Bi, Tianshu
Li, Jingyi
Zhang, Peng
Mitchell‐Colgan, Elliot
Xiao, Shiwu - Abstract:
- Abstract : Multiple sub‐/super‐synchronous frequency components were detected when sub‐synchronous oscillation (SSO) occured in permanent magent synchronous generator (PMSG)‐based wind farm in Northwest China. This caused three 600 MW turbine generators to trip because of torsional oscillation of the shaft. Then for one year, for eliminating the multiple frequency components, the relevant wind farms have been tripped for 111 times. The tripped wind power sometimes could even be up to 300 MW. However, the multiple frequency components' producing mechanism is still not clear. This study explains the mechanism by analysing the response characteristics of grid‐side converter (GSC) controller to the sub‐synchronous frequency component. When a sub‐synchronous frequency component is fed into GSC controller as an input signal, the expression for the output signal is derived. Furthermore, the frequency transformation relationship between input and output signals, the amplitudes of multiple frequency components in output signals are all discussed in detail. The theoretical analysis is then validated by the simulation results and the on‐site data measured by the phasor measurement unit (PMU). With the theoretical analysis, the main frequency components which should be suppressed are determined. The multiple frequency components can be mitigated not by tripping wind farms any more. This is conducive to the accommodation of renewable energy.
- Is Part Of:
- IET renewable power generation. Volume 11:Issue 7(2017)
- Journal:
- IET renewable power generation
- Issue:
- Volume 11:Issue 7(2017)
- Issue Display:
- Volume 11, Issue 7 (2017)
- Year:
- 2017
- Volume:
- 11
- Issue:
- 7
- Issue Sort Value:
- 2017-0011-0007-0000
- Page Start:
- 966
- Page End:
- 972
- Publication Date:
- 2017-05-30
- Subjects:
- power convertors -- power grids -- permanent magnet generators -- synchronous generators -- wind power plants -- turbogenerators -- shafts -- power generation protection
PMSG -- subsynchronous frequency component -- subsynchronous oscillation -- permanent magnet synchronous generator -- wind farm -- Northwest China -- SSO -- multiple subsuper‐synchronous frequency component -- turbine generator -- shaft torsional oscillation -- protection device -- wind power tripping -- GSC controller -- grid‐side converter controller -- frequency transformation relationship -- renewable energy -- power 600 MW
Renewable energy sources -- Periodicals
333.79405 - Journal URLs:
- http://digital-library.theiet.org/content/journals/iet-rpg ↗
http://ieeexplore.ieee.org/servlet/opac?punumber=4159946 ↗
http://www.ietdl.org/IET-RPG ↗
https://ietresearch.onlinelibrary.wiley.com/journal/17521424 ↗
http://www.theiet.org/ ↗ - DOI:
- 10.1049/iet-rpg.2016.0994 ↗
- Languages:
- English
- ISSNs:
- 1752-1416
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4363.253450
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: