Improved secant method for getting proper initial magnetization in transformer DC bias simulation. (December 2018)
- Record Type:
- Journal Article
- Title:
- Improved secant method for getting proper initial magnetization in transformer DC bias simulation. (December 2018)
- Main Title:
- Improved secant method for getting proper initial magnetization in transformer DC bias simulation
- Authors:
- Lu, Hailiang
Zhang, Jingzhuo
Yang, Fenyan
Xu, Baiyu
Liu, Zhengfu
Zheng, Zhihui
Lan, Lei
Wen, Xishan - Abstract:
- Highlights: A simulation model of transformer under DC bias is proposed. The influence of initial magnetization on simulation process is analyzed. An improved secant method for getting proper initial magnetization is proposed. Abstract: Geomagnetically – Induced Currents (GIC) and monopole operation of high voltage direct current (HVDC) both can cause transformer DC bias, and Jiles-Atherton (JA) model is effective in transformer DC bias simulation while the influence of initial magnetization is neglected in existing papers. In this paper, the influence of initial magnetization and magnetizing current on simulation process are analysed based on the presented simulation model, and the conclusion that initial magnetization has evident influence while initial magnetizing current has not is reached. The trend of magnetizing current is valued by representative slope of envelop curve, then an improved secant method for getting proper initial magnetization is proposed basing on the slope. With the method, the dependence of proper initial magnetization on DC current and closing angle are presented, and the mechanization is analysed.
- Is Part Of:
- International journal of electrical power & energy systems. Volume 103(2018)
- Journal:
- International journal of electrical power & energy systems
- Issue:
- Volume 103(2018)
- Issue Display:
- Volume 103, Issue 2018 (2018)
- Year:
- 2018
- Volume:
- 103
- Issue:
- 2018
- Issue Sort Value:
- 2018-0103-2018-0000
- Page Start:
- 50
- Page End:
- 57
- Publication Date:
- 2018-12
- Subjects:
- Transformer DC bias -- Initial magnetization -- Jiles-Atherton model -- Secant method
Electrical engineering -- Periodicals
Electric power systems -- Periodicals
Électrotechnique -- Périodiques
Réseaux électriques (Énergie) -- Périodiques
Electric power systems
Electrical engineering
Periodicals
621.3 - Journal URLs:
- http://www.sciencedirect.com/science/journal/01420615 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.ijepes.2018.05.030 ↗
- Languages:
- English
- ISSNs:
- 0142-0615
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.220000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 17028.xml