Maximum undergrounding degree of HV subtransmission networks as dictated by unscheduled power flows. Issue 11 (1st November 2013)
- Record Type:
- Journal Article
- Title:
- Maximum undergrounding degree of HV subtransmission networks as dictated by unscheduled power flows. Issue 11 (1st November 2013)
- Main Title:
- Maximum undergrounding degree of HV subtransmission networks as dictated by unscheduled power flows
- Authors:
- Lauria, Stefano
Palone, Francesco - Abstract:
- Abstract : Meshed HV subtransmission networks are subject to undesirable parallel (unscheduled) active power flows from the EHV system. The phenomenon is worsened by conversion of HV overhead lines to underground cables (UGCs), which increases parallel flows through the HV network because of the attendant reduction in HV line reactance; the effect increase with network extension and are compounded by UGC charging power. The study deals with the assessment of the maximum undergrounding degree for a given subtransmission network. An analytical formulation of maximum HV line extension length as a function of EHV power flow and undergrounding degree is given; optimum UGC shunt compensation requirements are evaluated. Application to a typical 150 kV–50 Hz network is presented, showing a very good agreement with power flow simulation. In particular, the case study evidences that complete undergrounding of the HV network is possible if line length is under 50 km; the proposed shunt compensation effectively raises this limit to 70 km.
- Is Part Of:
- IET generation, transmission & distribution. Volume 7:Issue 11(2013)
- Journal:
- IET generation, transmission & distribution
- Issue:
- Volume 7:Issue 11(2013)
- Issue Display:
- Volume 7, Issue 11 (2013)
- Year:
- 2013
- Volume:
- 7
- Issue:
- 11
- Issue Sort Value:
- 2013-0007-0011-0000
- Page Start:
- 1202
- Page End:
- 1209
- Publication Date:
- 2013-11-01
- Subjects:
- electric reactance -- load flow -- power overhead lines -- transmission networks -- underground cables
unscheduled power flow -- meshed HV subtransmission network -- active power flow -- EHV system -- underground cable -- HV line reactance -- UGC charging power -- maximum undergrounding degree -- optimum UGC shunt compensation requirement -- power flow simulation -- voltage 150 kV -- frequency 50 Hz
Electric power production -- Periodicals
Electric power transmission -- Periodicals
Electric power distribution -- Periodicals
621.3105 - Journal URLs:
- http://digital-library.theiet.org/content/journals/iet-gtd ↗
http://ieeexplore.ieee.org/servlet/opac?punumber=4082359 ↗
http://www.ietdl.org/IET-GTD ↗
https://ietresearch.onlinelibrary.wiley.com/journal/17518695 ↗
http://www.theiet.org/ ↗ - DOI:
- 10.1049/iet-gtd.2012.0295 ↗
- Languages:
- English
- ISSNs:
- 1751-8687
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4363.252540
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 16581.xml