Role of low‐voltage/NH fuselinks rated voltage in distribution network losses. An evaluation based on the Hellenic low‐voltage distribution network. Issue 5 (1st May 2014)
- Record Type:
- Journal Article
- Title:
- Role of low‐voltage/NH fuselinks rated voltage in distribution network losses. An evaluation based on the Hellenic low‐voltage distribution network. Issue 5 (1st May 2014)
- Main Title:
- Role of low‐voltage/NH fuselinks rated voltage in distribution network losses. An evaluation based on the Hellenic low‐voltage distribution network
- Authors:
- Psomopoulos, Constantinos S.
Ioannidis, George Ch.
Karras, Yannis - Abstract:
- Abstract : Protection of low‐voltage power lines is fuses' main application. In every distribution network, hundreds of thousands fuses are operating continuously. These components, because of their operating characteristics, present power losses widely known as 'power dissipation', which are increased as their rated voltage is increased. In this work, the potential reduction of power losses in the Hellenic low‐voltage distribution network by selecting fuses with voltage equal to the networks nominal (400 V), instead of 500 V or even 690 V, is examined. The presented analysis and results clearly show that the NH‐fuses' rated voltage should be equal to the networks nominal and not higher, which will result in reduced power losses and increased low‐voltage distribution network capacity, less thermal stress of the equipment, reduction of the primary energy needs and CO2 emissions. Furthermore, the proposed replacement leads to slightly less spare parts cost and could be implemented gradually during scheduled maintenance resulting zero implementation cost. Since Greece is not the only case of a country in which electrical distribution network operator applies the previous mentioned practice, it is rather obvious that the resultant conclusions could be very helpful for other countries which use similar regulation to reconsider and revise it.
- Is Part Of:
- IET generation, transmission & distribution. Volume 8:Issue 5(2014)
- Journal:
- IET generation, transmission & distribution
- Issue:
- Volume 8:Issue 5(2014)
- Issue Display:
- Volume 8, Issue 5 (2014)
- Year:
- 2014
- Volume:
- 8
- Issue:
- 5
- Issue Sort Value:
- 2014-0008-0005-0000
- Page Start:
- 803
- Page End:
- 810
- Publication Date:
- 2014-05-01
- Subjects:
- losses -- power distribution protection -- electric fuses -- power cables -- thermal stresses -- air pollution control
low voltage NH fuselinks rated voltage -- distribution network loss -- Hellenic low voltage distribution network -- low voltage power lines protection -- power loss reduction -- power dissipation -- fuse selection -- thermal stress -- primary energy reduction -- CO2 emission reduction -- scheduled maintenance -- electrical distribution network operator -- voltage 400 V
Electric power production -- Periodicals
Electric power transmission -- Periodicals
Electric power distribution -- Periodicals
621.3105 - Journal URLs:
- http://digital-library.theiet.org/content/journals/iet-gtd ↗
http://ieeexplore.ieee.org/servlet/opac?punumber=4082359 ↗
http://www.ietdl.org/IET-GTD ↗
https://ietresearch.onlinelibrary.wiley.com/journal/17518695 ↗
http://www.theiet.org/ ↗ - DOI:
- 10.1049/iet-gtd.2013.0520 ↗
- Languages:
- English
- ISSNs:
- 1751-8687
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4363.252540
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: