Study on the difference of chemical composition of insulator contamination on UHV‐AC and ‐DC transmission lines. Issue 1 (1st January 2018)
- Record Type:
- Journal Article
- Title:
- Study on the difference of chemical composition of insulator contamination on UHV‐AC and ‐DC transmission lines. Issue 1 (1st January 2018)
- Main Title:
- Study on the difference of chemical composition of insulator contamination on UHV‐AC and ‐DC transmission lines
- Authors:
- Li, Lee
Jiang, Yunpeng
Lu, Ming
Liu, Zehui
Hua, Kui
Li, Zhe - Abstract:
- Abstract : For the ultra high voltage (UHV)‐DC and UHV‐AC transmission lines, their contamination characteristics are different. Thus, researching the contamination polluted degree of UHV‐AC and UHV‐DC lines by geoaccumulation index and enrichment factor method is an ingenious method. This study analyses and compares the chemical composition of contamination on parallel energised UHV‐DC (800 kV) and UHV‐AC (1000 kV) overhead transmission lines. The results indicate that the major cations of insulator contamination are Ca 2 +, and NH4 +, and the major anions of insulator contamination are SO4 2− and NO3 − both on UHV‐DC and UHV‐AC lines. For the UHV‐DC line, the concentrations of the same cations on the insulator bottom surface are higher than that of on the top surface. However, on the UHV‐AC line, the same cation concentrations on the bottom surface close to the one on the top surface. The metallic elements of Ca 2+ and Zn 2+ are in seriously polluted degree. Also, the polluted degree of contamination on UHV‐DC insulator is more serious than UHV‐AC insulator. This study considers that field charging plays an important role in accumulating contamination.
- Is Part Of:
- IET science, measurement & technology. Volume 12:Issue 1(2018)
- Journal:
- IET science, measurement & technology
- Issue:
- Volume 12:Issue 1(2018)
- Issue Display:
- Volume 12, Issue 1 (2018)
- Year:
- 2018
- Volume:
- 12
- Issue:
- 1
- Issue Sort Value:
- 2018-0012-0001-0000
- Page Start:
- 17
- Page End:
- 24
- Publication Date:
- 2018-01-01
- Subjects:
- contamination -- power overhead lines -- chemical analysis
chemical composition -- insulator contamination -- geoaccumulation index -- parallel energised UHV‐DC overhead transmission lines -- parallel energised UHV‐AC overhead transmission lines -- cation concentrations -- UHV‐DC insulator -- UHV‐AC insulator
Measurement -- Periodicals
Electrical engineering -- Periodicals
Electronics -- Periodicals
Nanotechnology -- Periodicals
Electromagnetism -- Periodicals
Medical instruments and apparatus -- Periodicals
621.3 - Journal URLs:
- https://ietresearch.onlinelibrary.wiley.com/loi/17518830 ↗
http://digital-library.theiet.org/content/journals/iet-smt ↗
http://ieeexplore.ieee.org/servlet/opac?punumber=4105888 ↗
http://www.theiet.org/ ↗
http://www.ietdl.org/IP-SMT ↗ - DOI:
- 10.1049/iet-smt.2017.0102 ↗
- Languages:
- English
- ISSNs:
- 1751-8822
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4363.253530
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 16605.xml