Comparison of internal grid topologies of offshore wind farms regarding reliability and economic performance metrics analysis. Issue 5 (8th February 2019)
- Record Type:
- Journal Article
- Title:
- Comparison of internal grid topologies of offshore wind farms regarding reliability and economic performance metrics analysis. Issue 5 (8th February 2019)
- Main Title:
- Comparison of internal grid topologies of offshore wind farms regarding reliability and economic performance metrics analysis
- Authors:
- Pereira, Tiago
Castro, Rui - Abstract:
- Abstract : Despite higher winds, the investment and operation and maintenance costs of offshore wind farms are still high as compared to onshore solutions. This highlights the importance of an increased reliability, because the occurrence of a failure can result in long downtimes due to inaccessibility of the site during harsh weather conditions. This study performs a reliability analysis of the internal grid of an offshore wind farm, comparing different topologies and their economic outcome. The research addresses both a redundancy between each pair of two strings (classical redundancy design) and a redundancy between already redundantly paired sets of strings (newly proposed redundancy design). The results show that the use of a redundancy scheme leads to a positive Net Present Value (NPV) and an interesting Internal Rate of Return (IRR), which can be an appealing investment. Moreover, it is more profitable to simply rate the cables to support normal operation conditions at rated power rather than increasing the cable ratings to support all failure scenarios. Overall, the topology that shows the best economic results combined with a good reliability is the topology with cable ratings based on regular conditions with a redundancy in the middle of the string between each pair of two strings.
- Is Part Of:
- IET renewable power generation. Volume 13:Issue 5(2019)
- Journal:
- IET renewable power generation
- Issue:
- Volume 13:Issue 5(2019)
- Issue Display:
- Volume 13, Issue 5 (2019)
- Year:
- 2019
- Volume:
- 13
- Issue:
- 5
- Issue Sort Value:
- 2019-0013-0005-0000
- Page Start:
- 750
- Page End:
- 761
- Publication Date:
- 2019-02-08
- Subjects:
- offshore installations -- power generation economics -- wind power plants -- investment -- profitability -- power generation planning -- redundancy -- reliability
internal grid topologies -- offshore wind farm -- economic performance metrics analysis -- higher winds -- investment -- maintenance costs -- increased reliability -- reliability analysis -- string -- classical redundancy design -- redundantly paired sets -- redundancy scheme -- interesting Internal Rate -- cable ratings -- economic results -- good reliability
Renewable energy sources -- Periodicals
333.79405 - Journal URLs:
- http://digital-library.theiet.org/content/journals/iet-rpg ↗
http://ieeexplore.ieee.org/servlet/opac?punumber=4159946 ↗
http://www.ietdl.org/IET-RPG ↗
https://ietresearch.onlinelibrary.wiley.com/journal/17521424 ↗
http://www.theiet.org/ ↗ - DOI:
- 10.1049/iet-rpg.2018.5474 ↗
- Languages:
- English
- ISSNs:
- 1752-1416
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4363.253450
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 16474.xml