A heat-powered ejector chiller working with low-GWP fluid R1233zd(E) (Part 1: Experimental results). (January 2021)
- Record Type:
- Journal Article
- Title:
- A heat-powered ejector chiller working with low-GWP fluid R1233zd(E) (Part 1: Experimental results). (January 2021)
- Main Title:
- A heat-powered ejector chiller working with low-GWP fluid R1233zd(E) (Part 1: Experimental results)
- Authors:
- Mahmoudian, Jafar
Rocchetti, Andrea
Mazzelli, Federico
Milazzo, Adriano - Abstract:
- Abstract: A prototype ejector chiller with nominal cooling power of 40 kW, designed according to the "CRMC" criterion, has been tested by our research group since 2011. The prototype has undergone several refinements and finally has been upgraded to R1233zd(E), which is non-flammable, has low-GWP and favourable thermodynamic properties, i.e. "dry-expansion" and moderate pressure at generator. In terms of saturation pressure curve, the new fluid is similar to R245fa, which was previously used in the prototype. Hence, R1233zd(E) has been basically used as a "drop-in" replacement. The ejector chiller was tested at different evaporation temperatures (2.5 to 10°C), typical of air conditioning applications. Saturation temperatures at generator from 95 to 105°C have been selected as representative of waste-heat recovery. The experimental findings prove that the CRMC ejector has a satisfactory performance with the new working fluid.
- Is Part Of:
- International journal of refrigeration. Volume 121(2021)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 121(2021)
- Issue Display:
- Volume 121, Issue 2021 (2021)
- Year:
- 2021
- Volume:
- 121
- Issue:
- 2021
- Issue Sort Value:
- 2021-0121-2021-0000
- Page Start:
- 1
- Page End:
- 9
- Publication Date:
- 2021-01
- Subjects:
- Ejector chiller -- CRMC -- R1233zd(E) -- Experimental method -- Drop-in low-GWP fluid
Refroidisseur à éjecteur -- Méthode de variation de la quantité de mouvement à vitesse constante (CRMC ou Constant Rate Momentum Change) -- R1233zd(E) -- Méthode expérimentale -- Fluide de substitution immédiate à faible PRP
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2020.10.015 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 15192.xml