Application of a novel approach of resistive‐type superconducting fault current limiter with a fast protection system in multi‐terminal direct current network. (17th August 2020)
- Record Type:
- Journal Article
- Title:
- Application of a novel approach of resistive‐type superconducting fault current limiter with a fast protection system in multi‐terminal direct current network. (17th August 2020)
- Main Title:
- Application of a novel approach of resistive‐type superconducting fault current limiter with a fast protection system in multi‐terminal direct current network
- Authors:
- Ayachi Amor, Yacine
Didier, Gaëtan
Hamoudi, Farid
Lubin, Thierry - Abstract:
- Summary: The key obstacle in the realization of multiterminal high‐voltage direct current (MTDC) grids is the lack of existing commercial protection that a device can withstand the DC fault. Although different HVDC circuit breaker technologies have been investigated and demonstrators tested by manufacturers, the innovation of such devices to ensure a reliable protection system has not been proven yet due to the maximum breaking capability limitation especially in MTDC grids. To this, a combination of superconducting fault current limiter (SFCL) technology with a fast DC circuit breaker could bring a solution to this bottleneck. In this work, a new application of an accurate model of resistive‐type SFCL (rSFCL) considering both the electrical and thermal behaviors is proposed to work together with a proactive hybrid DC circuit breaker (PHCB) to fulfill the whole system protection. The viability of the proposed approach is verified under a worst DC fault case‐scenario that imposed in a five‐terminal MTDC meshed grid. The numerical analysis and simulations are carried out using (EMTP‐rv) software, while the obtained results show how significantly the proposed rSFCL can reduce the fault current and enhance the breaking capability. Also, a positive interaction has been observed between the rSFCL and PHCB in terms of design sizing and operation performance. Abstract : A new application of the second‐generation high‐temperature superconductor (2G HTS) of resistive‐type SFCL (rSFCL)Summary: The key obstacle in the realization of multiterminal high‐voltage direct current (MTDC) grids is the lack of existing commercial protection that a device can withstand the DC fault. Although different HVDC circuit breaker technologies have been investigated and demonstrators tested by manufacturers, the innovation of such devices to ensure a reliable protection system has not been proven yet due to the maximum breaking capability limitation especially in MTDC grids. To this, a combination of superconducting fault current limiter (SFCL) technology with a fast DC circuit breaker could bring a solution to this bottleneck. In this work, a new application of an accurate model of resistive‐type SFCL (rSFCL) considering both the electrical and thermal behaviors is proposed to work together with a proactive hybrid DC circuit breaker (PHCB) to fulfill the whole system protection. The viability of the proposed approach is verified under a worst DC fault case‐scenario that imposed in a five‐terminal MTDC meshed grid. The numerical analysis and simulations are carried out using (EMTP‐rv) software, while the obtained results show how significantly the proposed rSFCL can reduce the fault current and enhance the breaking capability. Also, a positive interaction has been observed between the rSFCL and PHCB in terms of design sizing and operation performance. Abstract : A new application of the second‐generation high‐temperature superconductor (2G HTS) of resistive‐type SFCL (rSFCL) is working together with a proactive hybrid DC circuit breaker to fulfill safe protection for a five‐terminal HVDC meshed grid that attending to be a part of European TWENTIES project. … (more)
- Is Part Of:
- International transactions on electrical energy systems. Volume 30:Number 10(2020)
- Journal:
- International transactions on electrical energy systems
- Issue:
- Volume 30:Number 10(2020)
- Issue Display:
- Volume 30, Issue 10 (2020)
- Year:
- 2020
- Volume:
- 30
- Issue:
- 10
- Issue Sort Value:
- 2020-0030-0010-0000
- Page Start:
- n/a
- Page End:
- n/a
- Publication Date:
- 2020-08-17
- Subjects:
- electro‐magnetic transient program -- multi‐terminal HVDC grid -- proactive hybrid DC circuit breaker -- resistive‐type superconducting fault current limiter
Electric power -- Periodicals
Electric power systems -- Periodicals
Electrical engineering -- Periodicals
621.3 - Journal URLs:
- http://www3.interscience.wiley.com/cgi-bin/jtoc/106562716/all ↗
http://onlinelibrary.wiley.com/journal/10.1002/(ISSN)2050-7038 ↗
https://www.hindawi.com/journals/itees/ ↗
http://onlinelibrary.wiley.com/ ↗ - DOI:
- 10.1002/2050-7038.12568 ↗
- Languages:
- English
- ISSNs:
- 2050-7038
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 14835.xml