Experimental investigation on the pull-down performance of a -80°C ultra-low temperature freezer. (November 2020)
- Record Type:
- Journal Article
- Title:
- Experimental investigation on the pull-down performance of a -80°C ultra-low temperature freezer. (November 2020)
- Main Title:
- Experimental investigation on the pull-down performance of a -80°C ultra-low temperature freezer
- Authors:
- Wang, Haidan
Song, Yulong
Cao, Feng - Abstract:
- Highlights: The discharge temperature of LTC increased first and then decreased during the pull-down process. The maximum value of LTC discharge temperatures increased with the rise of startup temperature. The volumetric efficiency of HTC compressor deteriorated more obviously than that of LTC during the pull-down process. Abstract: This paper presents an experimental investigation on the pull-down performance of a -80°C ultra-low temperature freezer. Experiments were conducted in a two-stage cascade refrigeration system with an inner recuperative heat exchanger in low temperature cycle (LTC). In addition, the pull-down performances of the freezer were discussed on different startup temperatures ranging from -20°C to 24°C when the ambient temperature was fixed at 26°C. In this paper, the cooling process was divided into early start-up phase, rapid cooling phase and stable cooling phase, and it was found that thermal parameters changed obviously with the startup temperatures, especially in the rapid cooling phase. The experimental results showed that there were maximum discharge temperatures of LTC compressor during pull-down process, and the maximum values increased with the rise of startup temperatures. When the startup temperature was -20°C, the maximum discharge temperature of LTC compressor was 8.1% (11.6°C) lower than that when the startup temperature was 24°C. As two factors affecting the discharge temperature of LTC significantly, the superheating degree was the mainHighlights: The discharge temperature of LTC increased first and then decreased during the pull-down process. The maximum value of LTC discharge temperatures increased with the rise of startup temperature. The volumetric efficiency of HTC compressor deteriorated more obviously than that of LTC during the pull-down process. Abstract: This paper presents an experimental investigation on the pull-down performance of a -80°C ultra-low temperature freezer. Experiments were conducted in a two-stage cascade refrigeration system with an inner recuperative heat exchanger in low temperature cycle (LTC). In addition, the pull-down performances of the freezer were discussed on different startup temperatures ranging from -20°C to 24°C when the ambient temperature was fixed at 26°C. In this paper, the cooling process was divided into early start-up phase, rapid cooling phase and stable cooling phase, and it was found that thermal parameters changed obviously with the startup temperatures, especially in the rapid cooling phase. The experimental results showed that there were maximum discharge temperatures of LTC compressor during pull-down process, and the maximum values increased with the rise of startup temperatures. When the startup temperature was -20°C, the maximum discharge temperature of LTC compressor was 8.1% (11.6°C) lower than that when the startup temperature was 24°C. As two factors affecting the discharge temperature of LTC significantly, the superheating degree was the main influencing factor in rapid cooling phase, while the decrease of the evaporation and condensation pressures had a more significant effect in the stable cooling phase. Besides, the volumetric efficiency of high temperature cycle (HTC) compressor deteriorated more obviously during the pull-down process, and had higher potential for performance improvement compared with that of LTC. … (more)
- Is Part Of:
- International journal of refrigeration. Volume 119(2020)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 119(2020)
- Issue Display:
- Volume 119, Issue 2020 (2020)
- Year:
- 2020
- Volume:
- 119
- Issue:
- 2020
- Issue Sort Value:
- 2020-0119-2020-0000
- Page Start:
- 1
- Page End:
- 10
- Publication Date:
- 2020-11
- Subjects:
- Inter-stage volumetric ratio -- Ultra-low temperature freezer -- Two-stage cascade system -- Pull-down performance
Rapport volumétrique inter-étages -- Congélateur à ultra-basse température -- Système en cascade biétagé -- Performance de refroidissement
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2020.04.030 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 14548.xml