Energy-saving analysis of air source heat pump integrated with a water storage tank for heating applications. (August 2020)
- Record Type:
- Journal Article
- Title:
- Energy-saving analysis of air source heat pump integrated with a water storage tank for heating applications. (August 2020)
- Main Title:
- Energy-saving analysis of air source heat pump integrated with a water storage tank for heating applications
- Authors:
- Wu, Pin
Wang, Zhichao
Li, Xiaofeng
Xu, Zhaowei
Yang, Yingxia
Yang, Qiang - Abstract:
- Abstract: Due to declining fossil fuel reserves and environmental contamination, the use of air source heat pumps has become a significant alternative to fossil fuel heating. In this paper, a heating system using an air source heat pump integrated with a water storage tank was constructed, to improve the operating efficiency of the air source heat pump (ASHP) at low ambient temperatures. It ran under a novel operation strategy of ASHP heating and water storage tank charging during the daytime, ASHP switching off and the water storage tank discharging at night. Under this approach, the ASHPs always operated at higher ambient temperatures and switched off at lower ambient temperatures. The test system of the air source heat pump integrated with a water storage tank was installed and monitored long-term in a practical building in Beijing. According to the monitored data from December 1st, 2018 to March 11th, 2019, the daily average ambient temperature varied from −9.3 °C to 11.3 °C, while the daily average indoor temperature ranged from 21.0 °C to 23.0 °C. The ASHP's daily average coefficient of performance (COP) on the coldest day was 2.35, and the seasonal coefficient of performance (SCOP) was 2.95. As compared to the continuous operation mode, the ASHP's daily average COP was enhanced by 14.0% on the coldest day, and the SCOP has improved by 26.1%. The air source heat pump integrated with a water storage tank has significant energy-saving potential under this operationAbstract: Due to declining fossil fuel reserves and environmental contamination, the use of air source heat pumps has become a significant alternative to fossil fuel heating. In this paper, a heating system using an air source heat pump integrated with a water storage tank was constructed, to improve the operating efficiency of the air source heat pump (ASHP) at low ambient temperatures. It ran under a novel operation strategy of ASHP heating and water storage tank charging during the daytime, ASHP switching off and the water storage tank discharging at night. Under this approach, the ASHPs always operated at higher ambient temperatures and switched off at lower ambient temperatures. The test system of the air source heat pump integrated with a water storage tank was installed and monitored long-term in a practical building in Beijing. According to the monitored data from December 1st, 2018 to March 11th, 2019, the daily average ambient temperature varied from −9.3 °C to 11.3 °C, while the daily average indoor temperature ranged from 21.0 °C to 23.0 °C. The ASHP's daily average coefficient of performance (COP) on the coldest day was 2.35, and the seasonal coefficient of performance (SCOP) was 2.95. As compared to the continuous operation mode, the ASHP's daily average COP was enhanced by 14.0% on the coldest day, and the SCOP has improved by 26.1%. The air source heat pump integrated with a water storage tank has significant energy-saving potential under this operation strategy. Highlights: An integrated ASHP heating system was constructed in a novel operation strategy. The system was monitored by multiple measuring points and sensors for 78 days. The measured SCOP of ASHP was 2.95, improved by 26.1% to traditional mode. Daily COPs enhanced by 14.0%–42.9% with different ambient temperatures. Defrosting duration and electrical energy consumption were quantitatively analyzed. … (more)
- Is Part Of:
- Building and environment. Volume 180(2020)
- Journal:
- Building and environment
- Issue:
- Volume 180(2020)
- Issue Display:
- Volume 180, Issue 2020 (2020)
- Year:
- 2020
- Volume:
- 180
- Issue:
- 2020
- Issue Sort Value:
- 2020-0180-2020-0000
- Page Start:
- Page End:
- Publication Date:
- 2020-08
- Subjects:
- Air source heat pump (ASHP) -- Water storage tank -- Energy-saving analysis -- Combined operation strategy -- Seasonal coefficient of performance (SCOP)
Buildings -- Environmental engineering -- Periodicals
Building -- Research -- Periodicals
Constructions -- Technique de l'environnement -- Périodiques
Electronic journals
696 - Journal URLs:
- http://www.sciencedirect.com/science/journal/03601323 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.buildenv.2020.107029 ↗
- Languages:
- English
- ISSNs:
- 0360-1323
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 2359.355000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: