Assessment and optimisation of low-GWP refrigerants during two-phase heat transfer inside small-diameter smooth tubes. (September 2020)
- Record Type:
- Journal Article
- Title:
- Assessment and optimisation of low-GWP refrigerants during two-phase heat transfer inside small-diameter smooth tubes. (September 2020)
- Main Title:
- Assessment and optimisation of low-GWP refrigerants during two-phase heat transfer inside small-diameter smooth tubes
- Authors:
- Longo, Giovanni A.
Mancin, Simone
Righetti, Giulia
Zilio, Claudio
Brown, J. Steven - Abstract:
- Highlights: This paper presents an assessment of new low-GWP refrigerants. The assessment couples experimental measurements and theoretical analysis. The theoretical analysis is based on the total temperature penalisation (TTP) criteria. The TTP analysis was also used for process optimisation. Abstract: This paper presents an assessment of new low-GWP refrigerants through coupling the experimental measurement of thermal and hydraulic performances to a theoretical evaluation based on the Total Temperature Penalisation (TTP) criterion for the specific case study of two-phase heat transfer inside a small-diameter smooth tube. The TTP analysis was also used for process optimisation. The TTP analysis identifies R32 and two hydrocarbon refrigerants R290 and R1270 as the most suitable low-GWP substitutes for R410A and R404A, respectively. R152a, R1234yf and R1234ze(E) are appropriate low-GWP alternatives for R134a, while R1234ze(Z) and R1233zd(E) emerge as appropriate low-GWP, near drop-in substitutes for R245fa. HydroFluoroCarbon (HFC) and HydroFluoroOlefin (HFO) refrigerants possess values of the optimum mass velocity in two-phase heat transfer inside small-diameter smooth tubes nearly double that of HydroCarbon (HC) refrigerants, and the optimum mass velocities for in-tube condensation are generally much higher than those in flow boiling.
- Is Part Of:
- International journal of refrigeration. Volume 117(2020)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 117(2020)
- Issue Display:
- Volume 117, Issue 2020 (2020)
- Year:
- 2020
- Volume:
- 117
- Issue:
- 2020
- Issue Sort Value:
- 2020-0117-2020-0000
- Page Start:
- 61
- Page End:
- 70
- Publication Date:
- 2020-09
- Subjects:
- Assessment -- Optimisation -- GWP -- Small-diameter tubes -- Total temperature penalisation TTP
Évaluation -- Optimisation -- PRP -- Tubes de faible diamètre -- Pénalisation totale de température (TTP)
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2020.03.022 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: