Persistent Legionella contamination of water faucets in a tertiary hospital in Japan. (April 2020)
- Record Type:
- Journal Article
- Title:
- Persistent Legionella contamination of water faucets in a tertiary hospital in Japan. (April 2020)
- Main Title:
- Persistent Legionella contamination of water faucets in a tertiary hospital in Japan
- Authors:
- Nakamura, Itaru
Amemura-Maekawa, Junko
Kura, Fumiaki
Kobayashi, Takehito
Sato, Akihiro
Watanabe, Hidehiro
Matsumoto, Tetsuya - Abstract:
- Highlights: We evaluated feasible Legionella decontamination strategies in Japan. Monitoring contamination, hyper-chlorination, heating, and flushing were performed. One thousand four hundred thirty-nine environmental samples were collected; 19 (1.3%) samples tested positive. Eight environmental isolates and two clinical isolates were genetically indistinguishable. The number of positive locations of hospital environments gradually decreased. Abstract: Objective: The feasibility of the decontamination procedure for Legionella pneumophila of water systems in healthcare facilities varies by water purification and disinfection methods in each country. We evaluated the efficacy of feasible decontamination strategies in Japan. Methods: This study was conducted at Tokyo Medical University Hospital (1015 beds) between 2015 and 2018. Samples from the water system and cooling tower were cultured periodically. Hyper-chlorination of cool tap water (>0.2 ppm), increases in the temperature of hot water (>55 °C), and flushing were used as decontamination strategies. The case of healthcare-associated legionellosis was surveyed. Environmental and clinical isolates were genotyped. Results: 1439 environmental samples were collected; 19 (1.3%) samples tested positive for L. pneumophila from water faucets of patient rooms, toilets, waste rooms, and water sourced from wells. Genotyping of 12 isolates confirmed that the same strains were present in eight environmental isolates and two isolatesHighlights: We evaluated feasible Legionella decontamination strategies in Japan. Monitoring contamination, hyper-chlorination, heating, and flushing were performed. One thousand four hundred thirty-nine environmental samples were collected; 19 (1.3%) samples tested positive. Eight environmental isolates and two clinical isolates were genetically indistinguishable. The number of positive locations of hospital environments gradually decreased. Abstract: Objective: The feasibility of the decontamination procedure for Legionella pneumophila of water systems in healthcare facilities varies by water purification and disinfection methods in each country. We evaluated the efficacy of feasible decontamination strategies in Japan. Methods: This study was conducted at Tokyo Medical University Hospital (1015 beds) between 2015 and 2018. Samples from the water system and cooling tower were cultured periodically. Hyper-chlorination of cool tap water (>0.2 ppm), increases in the temperature of hot water (>55 °C), and flushing were used as decontamination strategies. The case of healthcare-associated legionellosis was surveyed. Environmental and clinical isolates were genotyped. Results: 1439 environmental samples were collected; 19 (1.3%) samples tested positive for L. pneumophila from water faucets of patient rooms, toilets, waste rooms, and water sourced from wells. Genotyping of 12 isolates confirmed that the same strains were present in eight environmental isolates and two isolates from patients over three years. Although the environmental contamination of the water system was persistent, the number of positive locations of hospital environments gradually decreased; eight in 2015, four in 2016, three in 2017, and four in 2018, respectively. Conclusions: Monitoring contamination, hyper-chlorination, controlling temperature, and flushing were effective as a Legionella decontamination strategy. … (more)
- Is Part Of:
- International journal of infectious diseases. Volume 93(2020)
- Journal:
- International journal of infectious diseases
- Issue:
- Volume 93(2020)
- Issue Display:
- Volume 93, Issue 2020 (2020)
- Year:
- 2020
- Volume:
- 93
- Issue:
- 2020
- Issue Sort Value:
- 2020-0093-2020-0000
- Page Start:
- 300
- Page End:
- 304
- Publication Date:
- 2020-04
- Subjects:
- Tap water -- Legionellosis -- Legionnaires' disease -- Infection control -- Disinfectant -- Decontamination
Communicable diseases -- Periodicals
Communicable Diseases -- Periodicals
Communicable diseases
Periodicals
Electronic journals
616.9 - Journal URLs:
- http://bibpurl.oclc.org/web/73769 ↗
http://www.journals.elsevier.com/international-journal-of-infectious-diseases/ ↗
http://www.sciencedirect.com/science/journal/12019712 ↗
http://www.clinicalkey.com/dura/browse/journalIssue/12019712 ↗
http://www.clinicalkey.com.au/dura/browse/journalIssue/12019712 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.ijid.2020.03.002 ↗
- Languages:
- English
- ISSNs:
- 1201-9712
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.304750
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 13420.xml