Determining an accurate fault location in electrical energy distribution networks in the presence of DGs using transient analysis. (February 2020)
- Record Type:
- Journal Article
- Title:
- Determining an accurate fault location in electrical energy distribution networks in the presence of DGs using transient analysis. (February 2020)
- Main Title:
- Determining an accurate fault location in electrical energy distribution networks in the presence of DGs using transient analysis
- Authors:
- Gord, Ehsan
Dashti, Rahman
Najafi, Mojtaba
Santos, Athila Quaresma
Shaker, Hamid Reza - Abstract:
- Highlights: Fault location in Distribution Networks in the Presence of DGs is addressed. The proposed method is a novel two-steps approach. The method improves the state-of-art approaches in terms of accuracy. The method improves the state-of-art approaches in terms of the success rate. A good performance is confirmed in simulation and in the laboratory environment. Abstract: Distributed generation resources are becoming more popular in electric energy distribution networks. As more Distributed generation are integrated into the grid, the system performance is challenged by issues such as manifold power injection to the network or nonlinear behavior when a fault occurs. To address this, fault location in electric energy distribution networks in the presence of distributed generation needs particular attention. This is important to reduce the loss of generated energy, reduce interruptions time, increase the reliability of the network and consequently improve the security of electricity supply. In this paper, a novel fault location method is presented applied to distributed networks with distributed generation. The proposed method is a hybrid two-step method which identifies accurate fault location using information stored in the network at pre- and post-fault time. The proposed method employs voltage and current information at the beginning of the feeder to estimate fault distance in the first step. The estimated distance will be associated with several similar sectionsHighlights: Fault location in Distribution Networks in the Presence of DGs is addressed. The proposed method is a novel two-steps approach. The method improves the state-of-art approaches in terms of accuracy. The method improves the state-of-art approaches in terms of the success rate. A good performance is confirmed in simulation and in the laboratory environment. Abstract: Distributed generation resources are becoming more popular in electric energy distribution networks. As more Distributed generation are integrated into the grid, the system performance is challenged by issues such as manifold power injection to the network or nonlinear behavior when a fault occurs. To address this, fault location in electric energy distribution networks in the presence of distributed generation needs particular attention. This is important to reduce the loss of generated energy, reduce interruptions time, increase the reliability of the network and consequently improve the security of electricity supply. In this paper, a novel fault location method is presented applied to distributed networks with distributed generation. The proposed method is a hybrid two-step method which identifies accurate fault location using information stored in the network at pre- and post-fault time. The proposed method employs voltage and current information at the beginning of the feeder to estimate fault distance in the first step. The estimated distance will be associated with several similar sections considering the topology of the distributed networks. In the second step, the proposed method determines accurate fault location through transient analysis based on the frequency component. In this step, the exact fault location is identified. In order to investigate its performance, a standard IEEE-11 network is simulated in MATLAB. Furthermore, experiments are carried out in a network power simulator, showing good results. … (more)
- Is Part Of:
- Measurement. Volume 151(2020)
- Journal:
- Measurement
- Issue:
- Volume 151(2020)
- Issue Display:
- Volume 151, Issue 2020 (2020)
- Year:
- 2020
- Volume:
- 151
- Issue:
- 2020
- Issue Sort Value:
- 2020-0151-2020-0000
- Page Start:
- Page End:
- Publication Date:
- 2020-02
- Subjects:
- Distribution system -- Fault location -- Transient analysis -- Distributed generation
Weights and measures -- Periodicals
Measurement -- Periodicals
Measurement
Weights and measures
Periodicals
530.8 - Journal URLs:
- http://www.sciencedirect.com/science/journal/02632241 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.measurement.2019.107270 ↗
- Languages:
- English
- ISSNs:
- 0263-2241
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 5413.544700
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 12579.xml