Evaluation of thermal environment by coupling CFD analysis and wireless-sensor measurements of a full-scale room with cooling system. (February 2019)
- Record Type:
- Journal Article
- Title:
- Evaluation of thermal environment by coupling CFD analysis and wireless-sensor measurements of a full-scale room with cooling system. (February 2019)
- Main Title:
- Evaluation of thermal environment by coupling CFD analysis and wireless-sensor measurements of a full-scale room with cooling system
- Authors:
- Shan, Xiaofang
Xu, Wei
Lee, Yi-Kuen
Lu, Wei-Zhen - Abstract:
- Graphical abstract: Highlights: Indoor ventilation scheme of a fan coil unit cooling system is simulated. Wire-less room sensors are adopted to assist and validate CFD simulations. Radiant temperature asymmetry is analyzed inside the model room. PMV values at occupied zone vary from −0.75 to +0.75 under the cooling system. Abstract: HVAC systems are utilized to construct a thermally comfortable environment for occupants. As people spend more than 90% of time indoors, thermal conditions of indoor environment constructed by HVAC systems demand precise assessment. Predicted mean vote (PMV), a synthesized index, can reveal thermal conditions by evaluating occupants' thermal sensations. Four environmental parameters affecting PMV: air temperature, air speed, radiant temperature and relative humidity. This study integrates CFD simulations and wireless-sensor measurements to assess distributions of PMV considering radiation models. The distributions of environmental parameters: velocity, temperature, radiant temperature, inside an office room with fan coil unit (FCU) are firstly presented. Based on these distributions, spatial profiles of PMV are obtained to intuitively illustrate thermal conditions. Combined with experimental database collected by thermal-flow wireless-sensors, CFD simulations offer detailed predictions of indoor airflow and thermal parameters. The mean temperature at occupied zone is 23.3 °C agreeing well with set-point temperature 23 °C. Furthermore, velocityGraphical abstract: Highlights: Indoor ventilation scheme of a fan coil unit cooling system is simulated. Wire-less room sensors are adopted to assist and validate CFD simulations. Radiant temperature asymmetry is analyzed inside the model room. PMV values at occupied zone vary from −0.75 to +0.75 under the cooling system. Abstract: HVAC systems are utilized to construct a thermally comfortable environment for occupants. As people spend more than 90% of time indoors, thermal conditions of indoor environment constructed by HVAC systems demand precise assessment. Predicted mean vote (PMV), a synthesized index, can reveal thermal conditions by evaluating occupants' thermal sensations. Four environmental parameters affecting PMV: air temperature, air speed, radiant temperature and relative humidity. This study integrates CFD simulations and wireless-sensor measurements to assess distributions of PMV considering radiation models. The distributions of environmental parameters: velocity, temperature, radiant temperature, inside an office room with fan coil unit (FCU) are firstly presented. Based on these distributions, spatial profiles of PMV are obtained to intuitively illustrate thermal conditions. Combined with experimental database collected by thermal-flow wireless-sensors, CFD simulations offer detailed predictions of indoor airflow and thermal parameters. The mean temperature at occupied zone is 23.3 °C agreeing well with set-point temperature 23 °C. Furthermore, velocity values are below draft sensation limitations. The distribution of PMV indicates the cooling system is capable to construct thermally comfortable environment for occupants as well as the draft sensation conforming the satisfactory status. The research outputs provide useful information for designers of cooling system to build a comfortable indoor environment. … (more)
- Is Part Of:
- Sustainable cities and society. Volume 45(2019)
- Journal:
- Sustainable cities and society
- Issue:
- Volume 45(2019)
- Issue Display:
- Volume 45, Issue 2019 (2019)
- Year:
- 2019
- Volume:
- 45
- Issue:
- 2019
- Issue Sort Value:
- 2019-0045-2019-0000
- Page Start:
- 395
- Page End:
- 405
- Publication Date:
- 2019-02
- Subjects:
- Wireless sensors -- CFD simulation -- Thermal comfort -- Radiation model -- FCU cooling system
Sustainable urban development -- Periodicals
Sustainable buildings -- Periodicals
Urban ecology (Sociology) -- Periodicals
307.76 - Journal URLs:
- http://www.sciencedirect.com/science/journal/22106707/ ↗
http://www.sciencedirect.com/ ↗
http://www.journals.elsevier.com/sustainable-cities-and-society ↗ - DOI:
- 10.1016/j.scs.2018.12.011 ↗
- Languages:
- English
- ISSNs:
- 2210-6707
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 11952.xml