Energy saving obtainable by applying a commercially available M-cycle evaporative cooling system to the air conditioning of an office building in North Italy. (15th July 2019)
- Record Type:
- Journal Article
- Title:
- Energy saving obtainable by applying a commercially available M-cycle evaporative cooling system to the air conditioning of an office building in North Italy. (15th July 2019)
- Main Title:
- Energy saving obtainable by applying a commercially available M-cycle evaporative cooling system to the air conditioning of an office building in North Italy
- Authors:
- Zanchini, Enzo
Naldi, Claudia - Abstract:
- Abstract: We analyze the energy saving obtainable by coupling a commercially available M-cycle evaporative cooling system to a conventional refrigeration cycle, for the air conditioning of office buildings in North Italy. The analysis is performed through the dynamic simulation of a case study. The hourly energy needs for cooling, dehumidifying and air change, during July and August, of a real office building located in Milan are considered. The climate of Milan is humid in summer, so that the example refers to critical conditions for the application of this technology in Italy. Two systems with M-cycle evaporative cooling are analyzed and compared to a traditional system: M-cycle pre-cooling of the external air, coupled to a refrigeration cycle; M-cycle cooling of the recirculated air, coupled to a refrigeration cycle with heat recovery. The results show that the second application of the M-cycle offers the best performance: it yields a 37.6% reduction in energy extracted by the refrigeration cycle, a 76% reduction in heating energy, and a 38% reduction in the total use of electric energy, under the assumption of electric heating. The reduction in heating energy is due to avoiding reheating after dehumidification, without decrease in thermal comfort. Highlights: Combined M-cycle and refrigeration-cycle air conditioning systems are studied. The energy saving potential for office buildings in North Italy is analyzed. Commercially available M-cycle units and a real officeAbstract: We analyze the energy saving obtainable by coupling a commercially available M-cycle evaporative cooling system to a conventional refrigeration cycle, for the air conditioning of office buildings in North Italy. The analysis is performed through the dynamic simulation of a case study. The hourly energy needs for cooling, dehumidifying and air change, during July and August, of a real office building located in Milan are considered. The climate of Milan is humid in summer, so that the example refers to critical conditions for the application of this technology in Italy. Two systems with M-cycle evaporative cooling are analyzed and compared to a traditional system: M-cycle pre-cooling of the external air, coupled to a refrigeration cycle; M-cycle cooling of the recirculated air, coupled to a refrigeration cycle with heat recovery. The results show that the second application of the M-cycle offers the best performance: it yields a 37.6% reduction in energy extracted by the refrigeration cycle, a 76% reduction in heating energy, and a 38% reduction in the total use of electric energy, under the assumption of electric heating. The reduction in heating energy is due to avoiding reheating after dehumidification, without decrease in thermal comfort. Highlights: Combined M-cycle and refrigeration-cycle air conditioning systems are studied. The energy saving potential for office buildings in North Italy is analyzed. Commercially available M-cycle units and a real office building are considered. A traditional plant and two plants with M-cycle are simulated for two summer months. The best system yields 38% saving both in cooling energy and in electric energy. … (more)
- Is Part Of:
- Energy. Volume 179(2019)
- Journal:
- Energy
- Issue:
- Volume 179(2019)
- Issue Display:
- Volume 179, Issue 2019 (2019)
- Year:
- 2019
- Volume:
- 179
- Issue:
- 2019
- Issue Sort Value:
- 2019-0179-2019-0000
- Page Start:
- 975
- Page End:
- 988
- Publication Date:
- 2019-07-15
- Subjects:
- M-Cycle -- Evaporative cooling -- Air conditioning -- Office building -- Energy saving -- North Italy
Power resources -- Periodicals
Power (Mechanics) -- Periodicals
Energy consumption -- Periodicals
333.7905 - Journal URLs:
- http://www.elsevier.com/journals ↗
- DOI:
- 10.1016/j.energy.2019.05.065 ↗
- Languages:
- English
- ISSNs:
- 0360-5442
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3747.445000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 10981.xml