Optimum regeneration temperature of a desiccant solution in a packaged liquid desiccant-assisted air conditioning unit. (May 2019)
- Record Type:
- Journal Article
- Title:
- Optimum regeneration temperature of a desiccant solution in a packaged liquid desiccant-assisted air conditioning unit. (May 2019)
- Main Title:
- Optimum regeneration temperature of a desiccant solution in a packaged liquid desiccant-assisted air conditioning unit
- Authors:
- Dong, Hye-Won
Cho, Hye-Jin
Park, Joon-Young
Jeong, Jae-Weon - Abstract:
- Highlights: A series of experiments for a cross-flow regenerator with a lithium chloride desiccant solution was conducted. The regeneration effectiveness and energy performance were measured in a laboratory. The optimal regeneration temperature of the desiccant solution was 65 °C. Abstract: Recently, a package unit of liquid desiccant and an indirect and a direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) has been proposed. In this system, the amount of heating energy consumed to regenerate the desiccant solution is significant and should be reduced to achieve better energy conservation than that of a conventional air handling unit. The purpose of this research is to empirically investigate the optimum regeneration temperature of a lithium chloride (LiCl) desiccant solution, balancing the regeneration performance and solution heating energy consumption in the LD-IDECOAS package unit. The adiabatic cross-flow regenerator was tested in a test facility at desiccant solution temperatures of 50–90 °C. The measurement results were compared with the predicted data in the regenerator to assess the reliability of the experimental results. By balancing the regeneration performance with the solution heating energy consumption, the recommended temperature to regenerate the desiccant solution was 65 °C.
- Is Part Of:
- International journal of refrigeration. Volume 101(2019)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 101(2019)
- Issue Display:
- Volume 101, Issue 2019 (2019)
- Year:
- 2019
- Volume:
- 101
- Issue:
- 2019
- Issue Sort Value:
- 2019-0101-2019-0000
- Page Start:
- 155
- Page End:
- 166
- Publication Date:
- 2019-05
- Subjects:
- Regenerator -- Cross-flow configuration -- Liquid desiccant -- Lithium chloride solution -- Heat and mass transfer
Régénérateur -- Configuration en écoulements croisés -- Déshydratant liquide -- Solution de bromure de lithium -- Transfert de chaleur et de masse
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2019.03.037 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 10742.xml