Analysis of 500 kV OHTL polluted insulator string behavior during lightning strokes. (February 2018)
- Record Type:
- Journal Article
- Title:
- Analysis of 500 kV OHTL polluted insulator string behavior during lightning strokes. (February 2018)
- Main Title:
- Analysis of 500 kV OHTL polluted insulator string behavior during lightning strokes
- Authors:
- Said, A.
- Abstract:
- Highlights: The relation between 500 kV insulator string leakage current and flashover was analyzed. All case studies were done under normal condition and different lightning strokes. The harmonic spectrum and of clean and polluted 500-kV string insulators leakage current were detected. The relation between back flashover and insulator surface condition were discussed. Polluted insulator thermal losses magnitudes were 97.2% higher than in clean insulator. Low lightning strokes peak leaded to serious insulator flashover in case of polluted. Abstract: The lightning strokes can be very harmfull to the high voltage transmission lines especially in case polluted insulator string. In this paper, the lightning overvoltage in the El-Kuorimate - Cairo 500-kV transmission line single circuit is discussed. The leakage current and its harmonic spectrum on clean and polluted 500-kV string insulators are determined under normal condition and lightning strokes. Furthermore, the relation between back flashover and insulator surface condition are discussed under different magnitude of lightning strokes. The results show that the leakage current, thermal losses magnitudes in case polluted insulator are higher than in case clean insulator by about 97.2%. For polluted insulator, less lightning strokes peak will increase leakage current to above 60 mA, and lead to serious insulator flashover faster than clean insulator. This study based on an equivalent electrical model by using AlternativeHighlights: The relation between 500 kV insulator string leakage current and flashover was analyzed. All case studies were done under normal condition and different lightning strokes. The harmonic spectrum and of clean and polluted 500-kV string insulators leakage current were detected. The relation between back flashover and insulator surface condition were discussed. Polluted insulator thermal losses magnitudes were 97.2% higher than in clean insulator. Low lightning strokes peak leaded to serious insulator flashover in case of polluted. Abstract: The lightning strokes can be very harmfull to the high voltage transmission lines especially in case polluted insulator string. In this paper, the lightning overvoltage in the El-Kuorimate - Cairo 500-kV transmission line single circuit is discussed. The leakage current and its harmonic spectrum on clean and polluted 500-kV string insulators are determined under normal condition and lightning strokes. Furthermore, the relation between back flashover and insulator surface condition are discussed under different magnitude of lightning strokes. The results show that the leakage current, thermal losses magnitudes in case polluted insulator are higher than in case clean insulator by about 97.2%. For polluted insulator, less lightning strokes peak will increase leakage current to above 60 mA, and lead to serious insulator flashover faster than clean insulator. This study based on an equivalent electrical model by using Alternative Transients Program (ATP-EMTP) software. … (more)
- Is Part Of:
- International journal of electrical power & energy systems. Volume 95(2018)
- Journal:
- International journal of electrical power & energy systems
- Issue:
- Volume 95(2018)
- Issue Display:
- Volume 95, Issue 2018 (2018)
- Year:
- 2018
- Volume:
- 95
- Issue:
- 2018
- Issue Sort Value:
- 2018-0095-2018-0000
- Page Start:
- 405
- Page End:
- 416
- Publication Date:
- 2018-02
- Subjects:
- Lightning strokes -- Polluted insulator -- Leakage currents -- Back flashover
ATP-EMTP Alternative Transients Program-electromagnetic transients program -- G.W ground wire -- Ph phase -- LCC JMarti line cable conductor John Marti -- B field density -- J current density -- ρ soil resistivity -- εr relative permittivity -- μr relative permeability -- Vfo flashover voltage -- MCOV maximum continuous operating voltage -- Uc continuous operating voltage -- M1 to M6 tower name -- THD total harmonic distortion -- FFT fast Fourier transform -- Ip phase current -- G conductance -- Δx section length -- Zo surge impeadance -- V propagation velocity -- SA surge arrester
Electrical engineering -- Periodicals
Electric power systems -- Periodicals
Électrotechnique -- Périodiques
Réseaux électriques (Énergie) -- Périodiques
Electric power systems
Electrical engineering
Periodicals
621.3 - Journal URLs:
- http://www.sciencedirect.com/science/journal/01420615 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.ijepes.2017.09.010 ↗
- Languages:
- English
- ISSNs:
- 0142-0615
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.220000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: