Comparison of stationary and non-stationary wind-induced responses of a super-large cooling tower based on field measurements. (April 2019)
- Record Type:
- Journal Article
- Title:
- Comparison of stationary and non-stationary wind-induced responses of a super-large cooling tower based on field measurements. (April 2019)
- Main Title:
- Comparison of stationary and non-stationary wind-induced responses of a super-large cooling tower based on field measurements
- Authors:
- Ke, Shitang
Wang, Hao
Ge, Yaojun - Abstract:
- Abstract: Recent measurements made by our research group of a super-large cooling tower indicate that its fluctuations in wind-induced responses exhibit a degree of nonstationarity, echoing similar observations reported for other structures. This might cause errors in estimates of extreme responses and misunderstanding of wind-induced effects if nonstationarity is neglected. In this study, the wind-induced response signals of a super-large cooling tower (height 190 m) in a coastal region were measured for the first time under real Reynolds number and turbulent flow conditions. After noise reduction had been performed, nonstationarity of the signals was identified within various time intervals. The mean wind effect, pulsating wind effect, probability density distribution, dynamic amplification factor, and extreme responses of the super-large cooling tower were studied based on stationary and non-stationary models. Finally, the power spectral density (PSD) and evolutionary power spectral density (EPSD) of the wind-induced response signal were analyzed. The resonance spectral expression of wind-induced responses at resonance excitation points, which is applicable to super-large cooling towers, is summarized. The wind-induced responses presented strong nonstationarity. Non-stationary models that consider response nonstationarity are important in the authentic assessment of the extreme responses of super-large cooling towers. The extreme constant calculated by the stationaryAbstract: Recent measurements made by our research group of a super-large cooling tower indicate that its fluctuations in wind-induced responses exhibit a degree of nonstationarity, echoing similar observations reported for other structures. This might cause errors in estimates of extreme responses and misunderstanding of wind-induced effects if nonstationarity is neglected. In this study, the wind-induced response signals of a super-large cooling tower (height 190 m) in a coastal region were measured for the first time under real Reynolds number and turbulent flow conditions. After noise reduction had been performed, nonstationarity of the signals was identified within various time intervals. The mean wind effect, pulsating wind effect, probability density distribution, dynamic amplification factor, and extreme responses of the super-large cooling tower were studied based on stationary and non-stationary models. Finally, the power spectral density (PSD) and evolutionary power spectral density (EPSD) of the wind-induced response signal were analyzed. The resonance spectral expression of wind-induced responses at resonance excitation points, which is applicable to super-large cooling towers, is summarized. The wind-induced responses presented strong nonstationarity. Non-stationary models that consider response nonstationarity are important in the authentic assessment of the extreme responses of super-large cooling towers. The extreme constant calculated by the stationary model cannot provide an adequate assurance rate and reduces the economic efficiency of extreme response estimates. The vibration energy distributions of resonance excitation points in different regions of the cooling tower were similar, but the PSD functions at quasi-static points were dramatically different from each other. The energy distribution of the resonant excitation points showed a phased trend, and the proposed resonance spectral expression considers three stages of variation in the PSD function of the responses to achieve high predictive accuracy. Highlights: The wind-induced responses of a super-large cooling tower were acquired through field measurement for the first time. Non-stationary wind-induced effects of super-large cooling tower were investigated. Extreme response calculated by stationary model can't provide adequate assurance rate. The evolutionary power spectral density of wind-induced response was analyzed. The proposed resonance spectral expression achieves high prediction accuracy. … (more)
- Is Part Of:
- Thin-walled structures. Volume 137(2019)
- Journal:
- Thin-walled structures
- Issue:
- Volume 137(2019)
- Issue Display:
- Volume 137, Issue 2019 (2019)
- Year:
- 2019
- Volume:
- 137
- Issue:
- 2019
- Issue Sort Value:
- 2019-0137-2019-0000
- Page Start:
- 331
- Page End:
- 346
- Publication Date:
- 2019-04
- Subjects:
- Super-large cooling tower -- Field measurement -- Nonstationarity -- Extreme response -- Power spectrum analysis -- Time-frequency analysis
Thin-walled structures -- Periodicals
690.1 - Journal URLs:
- http://www.sciencedirect.com/science/journal/02638231 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.tws.2019.01.017 ↗
- Languages:
- English
- ISSNs:
- 0263-8231
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 8820.121000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 9620.xml