IEEE 1588 time synchronisation performance for IEC 61850 transmission substations. (May 2019)
- Record Type:
- Journal Article
- Title:
- IEEE 1588 time synchronisation performance for IEC 61850 transmission substations. (May 2019)
- Main Title:
- IEEE 1588 time synchronisation performance for IEC 61850 transmission substations
- Authors:
- Han, Mingyu
Guo, Hao
Crossley, Peter - Abstract:
- Highlights: Real time assessment of IEEE 1588 with multi-protocol traffic interactions. Combined GNSS and IEEE 1588 systems offer a more reliable timing performance. Manufactures have vendor-specific interpretations of IEEE 1588 messages. IEEE 1588 satisfies the ±1 μs accuracy requirement in transmission substations. Use capture card and impairment simulator to identify performance boundary. Abstract: Accurate timestamping with 1 µs precision is required by power system monitoring and control equipment, including: Phase Measurement Units (PMUs) for real-time measurement and control; travelling wave detectors for fault location, protection and control; and sample value measurement techniques associated with the IEC 61850 process bus. The conventional way of achieving this is to transmit 1-PPS or IRIG-B timing signals using dedicated cables but such an approach is expensive and difficult to update as secondary control systems evolve. IEEE 1588 precision time protocol (PTP) allows the transmission of time information with sub-microsecond accuracy in an Ethernet network. However, a comprehensive study is required to enhance the confidence of the power industry in using PTP in present and future IEC 61850 based substations. This paper delivers a design and experimental validation of the real-time time synchronisation characteristics achievable with IEEE 1588. Several factors which can potentially affect the synchronisation accuracy in delivering a time reference from the masterHighlights: Real time assessment of IEEE 1588 with multi-protocol traffic interactions. Combined GNSS and IEEE 1588 systems offer a more reliable timing performance. Manufactures have vendor-specific interpretations of IEEE 1588 messages. IEEE 1588 satisfies the ±1 μs accuracy requirement in transmission substations. Use capture card and impairment simulator to identify performance boundary. Abstract: Accurate timestamping with 1 µs precision is required by power system monitoring and control equipment, including: Phase Measurement Units (PMUs) for real-time measurement and control; travelling wave detectors for fault location, protection and control; and sample value measurement techniques associated with the IEC 61850 process bus. The conventional way of achieving this is to transmit 1-PPS or IRIG-B timing signals using dedicated cables but such an approach is expensive and difficult to update as secondary control systems evolve. IEEE 1588 precision time protocol (PTP) allows the transmission of time information with sub-microsecond accuracy in an Ethernet network. However, a comprehensive study is required to enhance the confidence of the power industry in using PTP in present and future IEC 61850 based substations. This paper delivers a design and experimental validation of the real-time time synchronisation characteristics achievable with IEEE 1588. Several factors which can potentially affect the synchronisation accuracy in delivering a time reference from the master clocks to the end devices during both steady-state and transient changes were investigated. The objective is to increase the understanding of the real-time performance of a complete IEEE 1588 timing system applied in transmission substations, and identify the limitations of commercially-available devices. … (more)
- Is Part Of:
- International journal of electrical power & energy systems. Volume 107(2019)
- Journal:
- International journal of electrical power & energy systems
- Issue:
- Volume 107(2019)
- Issue Display:
- Volume 107, Issue 2019 (2019)
- Year:
- 2019
- Volume:
- 107
- Issue:
- 2019
- Issue Sort Value:
- 2019-0107-2019-0000
- Page Start:
- 264
- Page End:
- 272
- Publication Date:
- 2019-05
- Subjects:
- Global Navigation Satellite Systems -- IEC 61850 -- IEEE 1588 -- Protection and control -- Substation automation
Electrical engineering -- Periodicals
Electric power systems -- Periodicals
Électrotechnique -- Périodiques
Réseaux électriques (Énergie) -- Périodiques
Electric power systems
Electrical engineering
Periodicals
621.3 - Journal URLs:
- http://www.sciencedirect.com/science/journal/01420615 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.ijepes.2018.11.036 ↗
- Languages:
- English
- ISSNs:
- 0142-0615
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.220000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 9405.xml