Energy and exergy analysis of a new ejector enhanced auto-cascade refrigeration cycle. (15th November 2015)
- Record Type:
- Journal Article
- Title:
- Energy and exergy analysis of a new ejector enhanced auto-cascade refrigeration cycle. (15th November 2015)
- Main Title:
- Energy and exergy analysis of a new ejector enhanced auto-cascade refrigeration cycle
- Authors:
- Yan, Gang
Chen, Jiaheng
Yu, Jianlin - Abstract:
- Highlights: A new ejector enhanced auto-cascade refrigeration cycle using R134a/R23 is proposed. The performance of new and basic cycles is compared by simulation method. The new cycle outperforms the basic cycle in both energetic and exergy aspects. Both cycles have optimum mixture compositions to obtain optimal performance. Abstract: A new ejector enhanced auto-cascade refrigeration cycle using R134a/R23 refrigerant mixture is proposed in this paper. In the new cycle, an ejector is used to recover part of the work that would otherwise be lost in the throttling processes. The performance comparison between the new cycle and a basic auto-cascade refrigeration cycle is carried out based on the first and second laws of thermodynamics. The simulation results show that both the coefficient of performance and exergy efficiency of the new cycle can be improved by 8.42–18.02% compared with those of the basic cycle at the same operation conditions as the ejector has achieved pressure lift ratios of 1.12–1.23. It is found that in the new cycle, the highest exergy destruction occurs in the compressor followed by the condenser, cascade condenser, expansion valve, ejector and evaporator. The effect of some main parameters on the cycle performance is further investigated. The results show that for the new cycle, the achieved performance improvement over the basic cycle is also dependent on the mixture composition and the vapor quality at the condenser outlet. The coefficient ofHighlights: A new ejector enhanced auto-cascade refrigeration cycle using R134a/R23 is proposed. The performance of new and basic cycles is compared by simulation method. The new cycle outperforms the basic cycle in both energetic and exergy aspects. Both cycles have optimum mixture compositions to obtain optimal performance. Abstract: A new ejector enhanced auto-cascade refrigeration cycle using R134a/R23 refrigerant mixture is proposed in this paper. In the new cycle, an ejector is used to recover part of the work that would otherwise be lost in the throttling processes. The performance comparison between the new cycle and a basic auto-cascade refrigeration cycle is carried out based on the first and second laws of thermodynamics. The simulation results show that both the coefficient of performance and exergy efficiency of the new cycle can be improved by 8.42–18.02% compared with those of the basic cycle at the same operation conditions as the ejector has achieved pressure lift ratios of 1.12–1.23. It is found that in the new cycle, the highest exergy destruction occurs in the compressor followed by the condenser, cascade condenser, expansion valve, ejector and evaporator. The effect of some main parameters on the cycle performance is further investigated. The results show that for the new cycle, the achieved performance improvement over the basic cycle is also dependent on the mixture composition and the vapor quality at the condenser outlet. The coefficient of performance improvement of the new cycle over the basic cycle degrades with increasing vapor quality. In addition, there exists an optimum mixture composition to obtain the maximum coefficient of performance for the new cycle when other operation conditions are given. The optimum mixture composition of both cycles may be fixed at about 0.5 under the given evaporating temperature. … (more)
- Is Part Of:
- Energy conversion and management. Volume 105(2016)
- Journal:
- Energy conversion and management
- Issue:
- Volume 105(2016)
- Issue Display:
- Volume 105, Issue 2016 (2016)
- Year:
- 2016
- Volume:
- 105
- Issue:
- 2016
- Issue Sort Value:
- 2016-0105-2016-0000
- Page Start:
- 509
- Page End:
- 517
- Publication Date:
- 2015-11-15
- Subjects:
- Zeotropic mixtures -- Auto-cascade refrigeration cycle -- Ejector -- Performance enhancement
Direct energy conversion -- Periodicals
Energy storage -- Periodicals
Energy transfer -- Periodicals
Énergie -- Conversion directe -- Périodiques
Direct energy conversion
Periodicals
621.3105 - Journal URLs:
- http://www.sciencedirect.com/science/journal/01968904 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.enconman.2015.07.087 ↗
- Languages:
- English
- ISSNs:
- 0196-8904
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3747.547000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 8271.xml