Empirical modeling of the impacts of faults on water-cooled chiller power consumption for use in building simulation programs. (25th April 2016)
- Record Type:
- Journal Article
- Title:
- Empirical modeling of the impacts of faults on water-cooled chiller power consumption for use in building simulation programs. (25th April 2016)
- Main Title:
- Empirical modeling of the impacts of faults on water-cooled chiller power consumption for use in building simulation programs
- Authors:
- Cheung, Howard
Braun, James E. - Abstract:
- Highlights: Developed empirical models to simulate chiller fault impacts in building models. Modeling of overcharging, excess oil, non-condensable, and condenser fouling. Predicted the amount of electricity and water consumption increase due to faults. Hotter and more humid climates worsen fault impacts. Abstract: Empirical models of four chiller faults that can be applied within existing building models to study overall impacts are developed in this paper. The faults include overcharging, excess oil, non-condensables in refrigerant and water-side condenser fouling. A single generalized model structured was developed for these faults that forces predicted fault impacts to be zero with no fault and increase with increasing fault level. The models were trained and tested using available laboratory data for a water-cooled centrifugal chiller where all four faults were artificially introduced. The fault model behavior was studied and then they were integrated in hospital models from DOE commercial reference building models (Deru et al., 2011) and simulations were performed in different climates. The simulation results showed maximum increases of building electricity consumption, electricity peak demand and water consumption of the hospitals due to faults of 4.7%, 7.8% and 1.8% respectively. The fault impacts were found to be more severe in hotter and more humid climates.
- Is Part Of:
- Applied thermal engineering. Volume 99(2016:Apr.)
- Journal:
- Applied thermal engineering
- Issue:
- Volume 99(2016:Apr.)
- Issue Display:
- Volume 99 (2016)
- Year:
- 2016
- Volume:
- 99
- Issue Sort Value:
- 2016-0099-0000-0000
- Page Start:
- 756
- Page End:
- 764
- Publication Date:
- 2016-04-25
- Subjects:
- Fault -- Chiller -- Empirical model -- Building simulation
Heat engineering -- Periodicals
Heating -- Equipment and supplies -- Periodicals
Periodicals
621.40205 - Journal URLs:
- http://www.sciencedirect.com/science/journal/13594311 ↗
http://www.elsevier.com/homepage/elecserv.htt ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.applthermaleng.2016.01.119 ↗
- Languages:
- English
- ISSNs:
- 1359-4311
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1580.101000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 7366.xml