Probabilistic and electricity saving analyses of Mist Coolers for Chiller System in a Hotel. (December 2017)
- Record Type:
- Journal Article
- Title:
- Probabilistic and electricity saving analyses of Mist Coolers for Chiller System in a Hotel. (December 2017)
- Main Title:
- Probabilistic and electricity saving analyses of Mist Coolers for Chiller System in a Hotel
- Authors:
- Yu, F.W.
Ho, W.T.
Chan, K.T.
Sit, R.K.Y. - Abstract:
- Abstract: This study investigates the optimization and electricity savings of an air-cooled chiller system with mist coolers. An air-cooled screw chiller having a nominal capacity of 282 kW was retrofitted with a mist cooler and dual condenser fan controls: fixed head pressure with constant speed and floating condensing temperature with variable speed. Comprehensive operating data logged at 5-min intervals were used to develop chiller models by random forest. The models served as a fitness function for genetic algorithm to predict the maximum coefficient of performance (COP) with optimal controlled variables under various operating conditions. Scatter plots of the optimal variables against the actual variables showed that to achieve the maximum COP, the set point of condensing temperature should be adjusted based on its measured value and the variation of heat rejection airflow rate. The probability of applying mist cooling was identified to be 70.91 – 78.33% for the simulated cooling load distribution of a hotel in a subtropical climate. Mist coolers with the optimal control brought electricity savings of 2.28 – 8.16%, depending on system configurations and condenser fan control modes. Fewer chillers in a system would result in more electricity savings from the optimal control while mist coolers complement the frequent full load operation of chillers to enhance electricity savings.
- Is Part Of:
- Energy procedia. Volume 143(2017)
- Journal:
- Energy procedia
- Issue:
- Volume 143(2017)
- Issue Display:
- Volume 143, Issue 2017 (2017)
- Year:
- 2017
- Volume:
- 143
- Issue:
- 2017
- Issue Sort Value:
- 2017-0143-2017-0000
- Page Start:
- 154
- Page End:
- 160
- Publication Date:
- 2017-12
- Subjects:
- Air-cooled chiller -- coefficient of performance -- genetic algorithm -- mist cooler -- random forest
Power resources -- Congresses
Power resources -- Periodicals
Power resources
Conference proceedings
Periodicals
333.7905 - Journal URLs:
- http://www.sciencedirect.com/science/journal/18766102 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.egypro.2017.12.664 ↗
- Languages:
- English
- ISSNs:
- 1876-6102
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3747.729700
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 5607.xml