Experimental assessment of a split air conditioner working with R-417A under different indoor and outdoor conditions. (January 2018)
- Record Type:
- Journal Article
- Title:
- Experimental assessment of a split air conditioner working with R-417A under different indoor and outdoor conditions. (January 2018)
- Main Title:
- Experimental assessment of a split air conditioner working with R-417A under different indoor and outdoor conditions
- Authors:
- Elgendy, E.
Melike, M.
Fatouh, M. - Abstract:
- Highlights: Performance of R-417A in split air conditioner is experimentally investigated. R-417A has the same pressure levels, lower discharge temperature as compared with R-22. Cooling capacity and COP increase as the indoor air relative humidity increases. Compared to R-22, cooling capacity and COP decrease using R-417A. Abstract: The present paper aims to evaluate the performance characteristics of a split air conditioner working with R-417A under different indoor and outdoor operating conditions. A test facility was constructed and experiments were carried out to achieve the research objectives. The indoor conditions were varied in a wide range of air temperature (21–31.4 °C), air relative humidity (40.3%–61.9%) and air velocity (2.8–4.7 m s −1 ) while the outdoor conditions were changed in range of air temperature (35–51.2 °C) and air relative humidity (40.8%–81.2%). Experimental results showed that the increase in the indoor air temperature causes an enhancement in the system coefficient of performance by about 59.7%, while increasing the outdoor air temperature decreases the system coefficient of performance by about 51.6%. The system cooling capacity using R-417A was lower than that of R-22 by about 33.2% at indoor air temperature of 24.5 °C.
- Is Part Of:
- International journal of refrigeration. Volume 85(2018)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 85(2018)
- Issue Display:
- Volume 85, Issue 2018 (2018)
- Year:
- 2018
- Volume:
- 85
- Issue:
- 2018
- Issue Sort Value:
- 2018-0085-2018-0000
- Page Start:
- 268
- Page End:
- 281
- Publication Date:
- 2018-01
- Subjects:
- R-417A -- Air conditioning -- Vapor compression refrigeration system, R-22 alternatives
AC air conditioner -- AHU air handling unit -- CC cooling coil -- EH electric heater -- EX.D expansion device -- FM flow meter -- GWP global warming potential -- H humidifier -- HC hydrocarbon -- HCFC hydrochlorofluorocarbon -- HFC hydrofluorocarbon -- HFO hydrofluoroolefins -- HP heat pump -- ODP ozone depletion potential -- V valve -- VCRS vapor compression refrigeration system -- WP water pump -- WS water source
R-417A -- Conditionnement d'air -- Système frigorifique à compression de vapeur -- Alternatives au R-22
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2017.10.005 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 5478.xml