New district heating system based on natural gas-fired boilers with absorption heat exchangers. (1st November 2017)
- Record Type:
- Journal Article
- Title:
- New district heating system based on natural gas-fired boilers with absorption heat exchangers. (1st November 2017)
- Main Title:
- New district heating system based on natural gas-fired boilers with absorption heat exchangers
- Authors:
- Sun, Fangtian
Zhao, Jinzi
Fu, Lin
Sun, Jian
Zhang, Shigang - Abstract:
- Abstract: Current district heating systems based on natural gas-fired boilers have lower primary energy efficiency due to its higher-temperature exhaust flue gas, and it cannot meet high-density heat load demand by the existing primary heating network. A new district heating system based on natural gas-fired boilers with absorption heat exchangers is presented to increase its primary energy efficiency and meet high-density heat load demand. In this new district heating system, absorption heat exchangers installed in heating substations could greatly decrease return water temperature of the primary heating network. The lower temperature return water could be used to cool exhaust flue gas and increase heat transmission capacity of the existing primary heating network. This new district heating system was analyzed by thermodynamics and economics. Results show that its primary energy efficiency and heat transmission capacity of the primary heating network are increased by about 11% and 47% respectively. When the heat transmission distance of the primary heating network is over 2.6 km, the new district heating system has better thermodynamic performance, economic benefit and environmental benefit, therefore, it would be a better choice for district heating systems based on natural gas-fired boilers with longer heat transmission distance of the primary heating network. Highlights: Absorption heat exchanger could decrease return water temperature greatly. Lower-temperature returnAbstract: Current district heating systems based on natural gas-fired boilers have lower primary energy efficiency due to its higher-temperature exhaust flue gas, and it cannot meet high-density heat load demand by the existing primary heating network. A new district heating system based on natural gas-fired boilers with absorption heat exchangers is presented to increase its primary energy efficiency and meet high-density heat load demand. In this new district heating system, absorption heat exchangers installed in heating substations could greatly decrease return water temperature of the primary heating network. The lower temperature return water could be used to cool exhaust flue gas and increase heat transmission capacity of the existing primary heating network. This new district heating system was analyzed by thermodynamics and economics. Results show that its primary energy efficiency and heat transmission capacity of the primary heating network are increased by about 11% and 47% respectively. When the heat transmission distance of the primary heating network is over 2.6 km, the new district heating system has better thermodynamic performance, economic benefit and environmental benefit, therefore, it would be a better choice for district heating systems based on natural gas-fired boilers with longer heat transmission distance of the primary heating network. Highlights: Absorption heat exchanger could decrease return water temperature greatly. Lower-temperature return water could increase primary energy efficiency by about 11%. Heating cost of new district heating system is reduced by 1.2–2.4 ¥/(m 2 a). New district heating system has better economic benefits and higher energy efficiency. New district heating system is suitable for longer heat transmission distance. … (more)
- Is Part Of:
- Energy. Volume 138(2017)
- Journal:
- Energy
- Issue:
- Volume 138(2017)
- Issue Display:
- Volume 138, Issue 2017 (2017)
- Year:
- 2017
- Volume:
- 138
- Issue:
- 2017
- Issue Sort Value:
- 2017-0138-2017-0000
- Page Start:
- 405
- Page End:
- 418
- Publication Date:
- 2017-11-01
- Subjects:
- Absorption heat exchanger -- Flue gas waste heat recovery -- High-density heat load -- District heating -- Energy-saving
Power resources -- Periodicals
Power (Mechanics) -- Periodicals
Energy consumption -- Periodicals
333.7905 - Journal URLs:
- http://www.elsevier.com/journals ↗
- DOI:
- 10.1016/j.energy.2017.07.030 ↗
- Languages:
- English
- ISSNs:
- 0360-5442
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 3747.445000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 5027.xml