A new under‐voltage load shedding scheme for islanded distribution system based on voltage stability indices. Issue 5 (4th May 2017)
- Record Type:
- Journal Article
- Title:
- A new under‐voltage load shedding scheme for islanded distribution system based on voltage stability indices. Issue 5 (4th May 2017)
- Main Title:
- A new under‐voltage load shedding scheme for islanded distribution system based on voltage stability indices
- Authors:
- Yusof, Nurul Aisyah
Mohd Rosli, Hazwani
Mokhlis, Hazlie
Karimi, Mazaher
Selvaraj, Jeyraj
Sapari, Norazliani Md - Abstract:
- Abstract : Under‐voltage load shedding (UVLS) is an important technique to maintain the voltage stability and frequency of a power system network. UVLS has been applied widely in transmission systems to avoid system blackouts. However, with increasing penetration of distributed generation such as photovoltaic (PV) systems, the application of UVLS becomes important for islanded distribution systems. Under this condition, the network does not have a frequency reference as when it is connected to the grid. In this condition, when the load demand exceeds the PV capacity, UVLS is the only option to stabilize the system by shedding the load based on the changes of the voltage magnitude. In this work, a new UVLS scheme based on voltage stability indices is proposed. Four voltage stability indices are used as indicators for load shedding. Based on the stability indices, the loads that have the highest tendency of voltage collapse shall be the first ones to be shed. The proposed scheme is tested on a practical distribution network energized by a grid, a mini hydro generator, and a PV system. The test results on various scenarios prove that the proposed method is able to restore the system stability. © 2017 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
- Is Part Of:
- IEEJ transactions on electrical and electronic engineering. Volume 12:Issue 5(2017)
- Journal:
- IEEJ transactions on electrical and electronic engineering
- Issue:
- Volume 12:Issue 5(2017)
- Issue Display:
- Volume 12, Issue 5 (2017)
- Year:
- 2017
- Volume:
- 12
- Issue:
- 5
- Issue Sort Value:
- 2017-0012-0005-0000
- Page Start:
- 665
- Page End:
- 675
- Publication Date:
- 2017-05-04
- Subjects:
- islanded distribution system -- distributed generation -- under‐voltage load shedding -- voltage stability index
Electrical engineering -- Periodicals
Electronics -- Periodicals
621.3 - Journal URLs:
- http://onlinelibrary.wiley.com/ ↗
- DOI:
- 10.1002/tee.22452 ↗
- Languages:
- English
- ISSNs:
- 1931-4973
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4363.240505
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 2943.xml