Thermodynamic investigation of parameters affecting the execution of steam injected cooled gas turbine based combined cycle power plant with vapor absorption inlet air cooling. (25th July 2017)
- Record Type:
- Journal Article
- Title:
- Thermodynamic investigation of parameters affecting the execution of steam injected cooled gas turbine based combined cycle power plant with vapor absorption inlet air cooling. (25th July 2017)
- Main Title:
- Thermodynamic investigation of parameters affecting the execution of steam injected cooled gas turbine based combined cycle power plant with vapor absorption inlet air cooling
- Authors:
- Shukla, Anoop Kumar
Singh, Onkar - Abstract:
- Highlights: Impact of combined effect of VAIAC, SI, and FC on the execution of CCPP is studied. Thermal efficiency of SGT cycle improves by 6.91% due to VAIAC scheme. Specific work output of SGT cycle increases by 16.41% due to VAIAC scheme. The integration of VAIAC, SI, and FC enhances the performances of CCPP. Abstract: Present paper deals with the thermodynamic investigation of influence of different parameters in steam injected cooled gas turbine based combined cycle power plant employing vapor absorption cooling of inlet air and two pressure heat recovery steam generator. Vapor absorption cooling scheme is run by utilizing the heat energy of the exhaust gas at the exit of HRSG. Gas turbine blades are cooled using film cooling technique. A study of the influence of ambient conditions, cycle pressure ratio, and turbine entry temperature on plant performance has been carried out. It has been noted that the efficiency of gas turbine improves by up to 6.91% and specific work output enhances by 16.42% with the integration of vapor absorption inlet air cooling to the simple cycle. The CCPP specific work output advances 17.34% at given turbine entry temperature as the steam to air ratio increases from 3% to 7% at the cycle pressure ratio of 24. Similarly thermal efficiency of CCPP increases by 6.78% for same cycle pressure ratio of 24 and the constant increment in steam to air ratio from 3 to 7%.
- Is Part Of:
- Applied thermal engineering. Volume 122(2017)
- Journal:
- Applied thermal engineering
- Issue:
- Volume 122(2017)
- Issue Display:
- Volume 122, Issue 2017 (2017)
- Year:
- 2017
- Volume:
- 122
- Issue:
- 2017
- Issue Sort Value:
- 2017-0122-2017-0000
- Page Start:
- 380
- Page End:
- 388
- Publication Date:
- 2017-07-25
- Subjects:
- Combined cycle -- Steam to air ratio -- Film cooling -- Vapor absorption
Heat engineering -- Periodicals
Heating -- Equipment and supplies -- Periodicals
Periodicals
621.40205 - Journal URLs:
- http://www.sciencedirect.com/science/journal/13594311 ↗
http://www.elsevier.com/homepage/elecserv.htt ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.applthermaleng.2017.05.034 ↗
- Languages:
- English
- ISSNs:
- 1359-4311
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1580.101000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 7.xml