Effect of undisturbed ground temperature on the design of closed-loop geothermal systems: A case study in a semi-urban environment. (15th August 2017)
- Record Type:
- Journal Article
- Title:
- Effect of undisturbed ground temperature on the design of closed-loop geothermal systems: A case study in a semi-urban environment. (15th August 2017)
- Main Title:
- Effect of undisturbed ground temperature on the design of closed-loop geothermal systems: A case study in a semi-urban environment
- Authors:
- Radioti, G.
Sartor, K.
Charlier, R.
Dewallef, P.
Nguyen, F. - Abstract:
- Highlights: High-resolution ground temperature profiles and comparison with numerical results. Error in ground temperature estimation from TRT data and impact on the design. Optimisation of BHEs design in urbanised areas. Abstract: This paper presents temperature measurements in four Borehole Heat Exchangers (BHEs), equipped with fiber optics and located in a semi-urban environment (campus of the University of Liege, Belgium). A 3D numerical model is also presented to simulate the heat loss from the surrounding structures into the subsurface. The mean undisturbed ground temperature was estimated from data during the preliminary phase of a thermal response test (water circulation in the pipe loops), as well as from borehole logging measurements. The measurements during water circulation can significantly overestimate the ground temperature (up to 1.7 °C in this case study) for high ambient air temperature during the test, resulting in an overestimation of the maximum extracted power and of the heat pump coefficient of performance (COP). To limit the error in the COP and the extracted power to less than 5%, the error in the undisturbed temperature estimation should not exceed ±1.5 °C and ±0.6 °C respectively. In urbanised areas, configurations of short BHEs (length < 40 m) could be economically advantageous (decreased installation and operation costs) compared to long BHEs, especially for temperature gradient lower than −0.05 °C/m.
- Is Part Of:
- Applied energy. Volume 200(2017)
- Journal:
- Applied energy
- Issue:
- Volume 200(2017)
- Issue Display:
- Volume 200, Issue 2017 (2017)
- Year:
- 2017
- Volume:
- 200
- Issue:
- 2017
- Issue Sort Value:
- 2017-0200-2017-0000
- Page Start:
- 89
- Page End:
- 105
- Publication Date:
- 2017-08-15
- Subjects:
- Undisturbed ground temperature -- TRT rig insulation -- Numerical modelling -- Urbanisation effect -- Design
Power (Mechanics) -- Periodicals
Energy conservation -- Periodicals
Energy conversion -- Periodicals
621.042 - Journal URLs:
- http://www.sciencedirect.com/science/journal/03062619 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.apenergy.2017.05.070 ↗
- Languages:
- English
- ISSNs:
- 0306-2619
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1572.300000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 729.xml