Alternative ventilation strategies in U.S. offices: Comprehensive assessment and sensitivity analysis of energy saving potential. (1st May 2017)
- Record Type:
- Journal Article
- Title:
- Alternative ventilation strategies in U.S. offices: Comprehensive assessment and sensitivity analysis of energy saving potential. (1st May 2017)
- Main Title:
- Alternative ventilation strategies in U.S. offices: Comprehensive assessment and sensitivity analysis of energy saving potential
- Authors:
- Rackes, Adams
Waring, Michael S. - Abstract:
- Abstract: Mature technologies exist to reduce the heating, ventilation, and air-conditioning (HVAC) energy associated with ventilation and use ventilation proactively to save energy. This study investigated the energy use impacts in U.S. office buildings of multiple alternative ventilation strategies that combined: economizing, demand controlled ventilation (DCV), supply air temperature reset (SR), and/or a doubled ventilation rate. We used energy simulations in a Monte Carlo analysis, sampling 17 building inputs and varying locations to match the climate zone distribution of the U.S. office stock. Results indicated the possibility for significant savings compared to a baseline that ventilated constantly at a minimum rate in both a small office type with a constant air volume (CAV) HVAC system and a medium office type with a variable air volume (VAV) system. In 95% of instances, HVAC source energy savings were 5–25% in the small-CAV office (median: 11%) and 6–42% in the medium-VAV office (median: 27%). In the small-CAV office, DCV typically saved the most energy, usually from heating, and heating degree days and occupant density were decisive influences. In the medium-VAV office, economizing and SR were most important, DCV usually only had minor impacts, and zone temperature setpoints, along with climate indicators, were the critical influences. Other than infiltration, envelope characteristics did not strongly influence energy impacts. The untapped primary energy savings ofAbstract: Mature technologies exist to reduce the heating, ventilation, and air-conditioning (HVAC) energy associated with ventilation and use ventilation proactively to save energy. This study investigated the energy use impacts in U.S. office buildings of multiple alternative ventilation strategies that combined: economizing, demand controlled ventilation (DCV), supply air temperature reset (SR), and/or a doubled ventilation rate. We used energy simulations in a Monte Carlo analysis, sampling 17 building inputs and varying locations to match the climate zone distribution of the U.S. office stock. Results indicated the possibility for significant savings compared to a baseline that ventilated constantly at a minimum rate in both a small office type with a constant air volume (CAV) HVAC system and a medium office type with a variable air volume (VAV) system. In 95% of instances, HVAC source energy savings were 5–25% in the small-CAV office (median: 11%) and 6–42% in the medium-VAV office (median: 27%). In the small-CAV office, DCV typically saved the most energy, usually from heating, and heating degree days and occupant density were decisive influences. In the medium-VAV office, economizing and SR were most important, DCV usually only had minor impacts, and zone temperature setpoints, along with climate indicators, were the critical influences. Other than infiltration, envelope characteristics did not strongly influence energy impacts. The untapped primary energy savings of alternative ventilation strategies over the 74% of U.S. office floorspace reasonably represented by our modeling was estimated at 36 TWh per year, with an annual value of U.S. $1.25 billion. Highlights: Ventilation strategies combining four mature technologies/changes were studied. Energy simulations, Monte Carlo sensitivity analysis modeled the U.S. office stock. HVAC energy savings were significant but highly sensitive to climate and building. Occupant density, internal gains, infiltration, and setpoints were most important. Strategies could save 16% of HVAC primary energy use in U.S. offices represented. … (more)
- Is Part Of:
- Building and environment. Volume 116(2017)
- Journal:
- Building and environment
- Issue:
- Volume 116(2017)
- Issue Display:
- Volume 116, Issue 2017 (2017)
- Year:
- 2017
- Volume:
- 116
- Issue:
- 2017
- Issue Sort Value:
- 2017-0116-2017-0000
- Page Start:
- 30
- Page End:
- 44
- Publication Date:
- 2017-05-01
- Subjects:
- Energy efficiency measures -- Building energy simulation -- Economizer -- Demand controlled ventilation -- Supply air temperature reset -- Heating, ventilation, and air-conditioning (HVAC)
Buildings -- Environmental engineering -- Periodicals
Building -- Research -- Periodicals
Constructions -- Technique de l'environnement -- Périodiques
Electronic journals
696 - Journal URLs:
- http://www.sciencedirect.com/science/journal/03601323 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.buildenv.2017.01.027 ↗
- Languages:
- English
- ISSNs:
- 0360-1323
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 2359.355000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 2589.xml