A three‐level temperature curve for power cables aging failure rate estimation incorporating load cycling. (16th July 2012)
- Record Type:
- Journal Article
- Title:
- A three‐level temperature curve for power cables aging failure rate estimation incorporating load cycling. (16th July 2012)
- Main Title:
- A three‐level temperature curve for power cables aging failure rate estimation incorporating load cycling
- Authors:
- Gilvanejad, Mojtaba
Abyaneh, Hossein Askarian
Mazlumi, Kazem - Abstract:
- SUMMARY: Useful lifetime of power cables and related aging failure rates mostly depends on thermal stresses that they experience because of the loss‐resulted heat inside the cable in normal or abnormal currents of the network. Knowing the real values of the cable aging failure rate is a key point, and the network operators should enable to estimate the related aging failure rates of their network cables. The already provided methods for cable transient temperature estimation require several different inputs as well as cable installation configuration data that are difficult to collect for operators. Hence, in this article, an artificial neural network–based approach is applied for estimation a cable maximum temperature, which serves a certain daily load curve. The artificial neural network only requires four inputs that are easy to provide. An experimental equation is then used for estimating the cable minimum temperature, and finally, a three‐level temperature curve is formed for cable aging failure rate estimation. The life fractions lost during each level of the predicted temperature curve are evaluated by resorting to an already existing combined electrothermal life model held for cable insulation. This method uses the life model and the probabilistic failure model to predict the failure rate of power cables for a future period. The results show that failure rate estimations are in good accordance with exact results, remarking that the estimated three‐level stepwiseSUMMARY: Useful lifetime of power cables and related aging failure rates mostly depends on thermal stresses that they experience because of the loss‐resulted heat inside the cable in normal or abnormal currents of the network. Knowing the real values of the cable aging failure rate is a key point, and the network operators should enable to estimate the related aging failure rates of their network cables. The already provided methods for cable transient temperature estimation require several different inputs as well as cable installation configuration data that are difficult to collect for operators. Hence, in this article, an artificial neural network–based approach is applied for estimation a cable maximum temperature, which serves a certain daily load curve. The artificial neural network only requires four inputs that are easy to provide. An experimental equation is then used for estimating the cable minimum temperature, and finally, a three‐level temperature curve is formed for cable aging failure rate estimation. The life fractions lost during each level of the predicted temperature curve are evaluated by resorting to an already existing combined electrothermal life model held for cable insulation. This method uses the life model and the probabilistic failure model to predict the failure rate of power cables for a future period. The results show that failure rate estimations are in good accordance with exact results, remarking that the estimated three‐level stepwise curve of cable temperature is a good approximation of cable thermal transients during cyclic loads. Copyright © 2012 John Wiley & Sons, Ltd. … (more)
- Is Part Of:
- International transactions on electrical energy systems. Volume 23:Number 6(2013:Sep.)
- Journal:
- International transactions on electrical energy systems
- Issue:
- Volume 23:Number 6(2013:Sep.)
- Issue Display:
- Volume 23, Issue 6 (2013)
- Year:
- 2013
- Volume:
- 23
- Issue:
- 6
- Issue Sort Value:
- 2013-0023-0006-0000
- Page Start:
- 853
- Page End:
- 866
- Publication Date:
- 2012-07-16
- Subjects:
- power cable -- three‐level temperature curve -- aging failure rate -- load cycling
Electric power -- Periodicals
Electric power systems -- Periodicals
Electrical engineering -- Periodicals
621.3 - Journal URLs:
- http://www3.interscience.wiley.com/cgi-bin/jtoc/106562716/all ↗
http://onlinelibrary.wiley.com/journal/10.1002/(ISSN)2050-7038 ↗
https://www.hindawi.com/journals/itees/ ↗
http://onlinelibrary.wiley.com/ ↗ - DOI:
- 10.1002/etep.1664 ↗
- Languages:
- English
- ISSNs:
- 2050-7038
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 83.xml