Experimental investigation on reverse cycle defrosting performance improvement for an ASHP unit by evenly adjusting the refrigerant distribution in its outdoor coil. (5th March 2017)
- Record Type:
- Journal Article
- Title:
- Experimental investigation on reverse cycle defrosting performance improvement for an ASHP unit by evenly adjusting the refrigerant distribution in its outdoor coil. (5th March 2017)
- Main Title:
- Experimental investigation on reverse cycle defrosting performance improvement for an ASHP unit by evenly adjusting the refrigerant distribution in its outdoor coil
- Authors:
- Song, Mengjie
Liu, Shengchun
Deng, Shiming
Sun, Zhili
Yan, Huaxia - Abstract:
- Abstract: For an air source heat pump (ASHP) unit, reverse cycle defrosting operations are always conducted to solve the undesired frosting problem. Previous studies verified that, uneven refrigerant distribution (URD) and melted frost downwards flowing (MFDF) along the vertically installed multi-circuit outdoor coil would degrade system defrosting performance. However, it is hardly possible to separate the URD and MFDF effects in a practical multi-circuit outdoor coil. In addition, it is a fundamental coupled problem of uneven heat and mass transfer. Consequently, to investigate the coupled effects of MFDF and URD on system defrosting performance, a sequential experimental study is carried out and reported in this paper. Firstly, a special testing facility and tailor-made three-circuit outdoor coil were introduced. This is followed by two experimental cases designed, with frost evenly accumulated on the surface of each circuit by adjusting the stop valves' opening degrees. After the experimental results compared, basing on refrigerant evenly and unevenly distributed into each circuit, energy analysis was also given. Finally, as concluded, the coupled effects were negative on system energy performance, and defrosting efficiency increased by 7.4%, from 40.5% to 47.9%, when the refrigerant's distribution changed from uneven to even. This study makes contributions on the optimization of system control strategies.
- Is Part Of:
- Applied thermal engineering. Volume 114(2017:Mar.)
- Journal:
- Applied thermal engineering
- Issue:
- Volume 114(2017:Mar.)
- Issue Display:
- Volume 114 (2017)
- Year:
- 2017
- Volume:
- 114
- Issue Sort Value:
- 2017-0114-0000-0000
- Page Start:
- 611
- Page End:
- 620
- Publication Date:
- 2017-03-05
- Subjects:
- Uneven refrigerant distribution -- Melted frost downwards flowing -- Multi-circuit outdoor coil -- Air source heat pump -- Experimental study -- Defrosting
Heat engineering -- Periodicals
Heating -- Equipment and supplies -- Periodicals
Periodicals
621.40205 - Journal URLs:
- http://www.sciencedirect.com/science/journal/13594311 ↗
http://www.elsevier.com/homepage/elecserv.htt ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.applthermaleng.2016.11.206 ↗
- Languages:
- English
- ISSNs:
- 1359-4311
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1580.101000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 2624.xml