Experimental Study on the Influence of Ventilated Window on Indoor Air Quality and Energy Consumption. (2016)
- Record Type:
- Journal Article
- Title:
- Experimental Study on the Influence of Ventilated Window on Indoor Air Quality and Energy Consumption. (2016)
- Main Title:
- Experimental Study on the Influence of Ventilated Window on Indoor Air Quality and Energy Consumption
- Authors:
- Zhang, Ningning
Jin, Wufeng
He, Junwei - Abstract:
- Abstract: The ventilated window has great potential on improving indoor air quality, but it may increase energy consumption. This paper studies the influence of different running modes of ventilated window on indoor PM2.5 and CO2 concentration and the overall energy consumption. When indoor PM2.5 concentration was more than 90ug/m 3, and outdoor PM2.5 concentration was less than 300ug/m 3 after ventilated window operating for an hour, indoor PM2.5 concentration decreased for 9-16%, it is appropriate to operating the ventilated window, but it was still 0.18-0.27 times more than the secondary standard. Operating the ventilated window for 55mins on mid-grade and high-grade respectively could reduce the increment of CO2 concentration for 3.31% and 22.19% than that without ventilated window operating. When the ventilated window operateing on low-grade, the increment of CO2 concentration was 11.34% larger than that without ventilated window operating. By increasing air volume and operating time of different modes, indoor air quality can be improved. Comparing with the condition with ventilated window off, the maximum energy consumption after ventilated window operating for 24 hours on high-grade was 2.462 kW·h -1 (2.054 kW·h -1 for air conditioning consumption). Appropriate operating mode and running time can be chosen to reduce energy consumption effectively.
- Is Part Of:
- Procedia engineering. Volume 146(2016)
- Journal:
- Procedia engineering
- Issue:
- Volume 146(2016)
- Issue Display:
- Volume 146, Issue 2016 (2016)
- Year:
- 2016
- Volume:
- 146
- Issue:
- 2016
- Issue Sort Value:
- 2016-0146-2016-0000
- Page Start:
- 296
- Page End:
- 302
- Publication Date:
- 2016
- Subjects:
- Indoor air quality -- Energy consumption -- Ventilated window -- PM2.5 -- CO2
Engineering -- Congresses
Engineering -- Periodicals
Engineering
Conference proceedings
Periodicals
620.005 - Journal URLs:
- http://www.sciencedirect.com/science/journal/18777058 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.proeng.2016.06.394 ↗
- Languages:
- English
- ISSNs:
- 1877-7058
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 1846.xml